Transformer fault diagnosis based on adversarial generative networks and deep stacked autoencoder

Lei Zhang1, Zhongyang Xu1, Chen Lu1

  • 1North China Branch of State Grid Corporation of China, China.

Heliyon
|May 20, 2024
PubMed
Summary

A conditional Wasserstein generative adversarial network with gradient penalty optimization (CWGAN-GP) effectively expands transformer oil chromatogram data. This method improves transformer fault diagnosis accuracy by over 4.98% compared to original imbalanced samples.

Related Concept Videos

Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
863
Types Of Transformers01:16

Types Of Transformers

Transformers can provide desired voltages to a circuit by modifying the number of turns in the secondary windings.
If the ratio of the number of turns in the secondary winding to that of the primary winding is greater than one, then the transformer is said to be a step-up transformer. In a step-up transformer, the voltage at the secondary winding is greater than the voltage applied at the primary winding.
However, if this ratio is less than one, the transformer is said to be a step-down...
968
Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
102
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
83
Transformers01:26

Transformers

A device that transforms voltages from one value to another using induction is called a transformer. A transformer consists of two separate coils, or windings, wrapped around the same soft iron core. However, they are electrically insulated from each other.
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
1.1K
The Ideal Transformer01:26

The Ideal Transformer

In single-phase two-winding transformers, two windings are coiled around a magnetic core characterized by cross-sectional area A and magnetic permeability μ. A phasor current i1 enters the left winding while i2 exits the right winding, establishing the fundamental working of the transformer through electromagnetic principles.
Ampere's Law forms the basis of understanding the magnetic field within the transformer. It states that the integral of the magnetic field intensity's...
379