Design, Instrumentation and Usage Protocols for Distributed In Situ Thermal Hot Spots Monitoring in Electric Coils using FBG Sensor Multiplexing
Published on: March 8, 2020
Distributed Vibration Monitoring System for 10 kV-400 kVA 3D Wound Core Transformer under Progressive Short-Circuit
Jiagui Tao1, Sicong Zhang1, Jianzhuo Dai1
1Electrical Power Academy of Sciences, State Grid of Jiangsu Electric Power Co., Ltd., Nanjing 210024, China.
Abstract:
As large-scale, high-proportion, and efficient distribution transformers surge into the grids, anti-short circuit capability testing of transformer windings in efficient distribution seems necessary and prominent. To deeply explore the influence of progressively short-circuit shock impulses on the core winding deformation of efficient power transformers, a finite element theoretical model was built by referring to a three-phase three-winding 3D wound core transformer with a model of S20-MRL-400/10-NX2. The distributions of internal equivalent force and total deformation of the 3D wound core transformer along different paths under progressively short-circuit shock impulses varying from 60% to 120% were investigated. Results show that the equivalent stress and total deformation change rate reach their maximum as the short-circuit current increases from 60% to 80%, and the maximum and average variation rate for the equivalent stress reach 177.75% and 177.43%, while the maximum and average variation rate for the total deformation corresponds to 178.30% and 177.45%, respectively. Meanwhile, the maximum equivalent stress and maximum total deformation reach 29.81 MPa and 38.70 μm, respectively, as the applied short-circuit current increased to 120%. In light of the above observations, the optimization and deployment of wireless sensor nodes was suggested. Therefore, a distributed monitoring system was developed for acquiring the vibration status of the windings in a 3D wound core transformer, which is a beneficial supplement to the traditional short-circuit reactance detection methods for an efficient grid access spot-check of distribution transformers.
Related Concept Videos
Instrument Transformers
Power System Three-Phase Short Circuits
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Transformers in Distribution System
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Three-Winding Transformers
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
Insulation Coordination