Security in Transformer Visual Trackers: A Case Study on the Adversarial Robustness of Two Models.

Peng Ye1,2,3, Yuanfang Chen1,2, Sihang Ma1,2

  • 1School of Cyberspace, Hangzhou Dianzi University, Hangzhou 310018, China.

PubMed
Summary

Transformer models in visual tracking are vulnerable to adversarial attacks. Researchers demonstrated that crafted adversarial examples can significantly degrade performance, with white-box attacks achieving over 90% success rates.

Related Concept Videos

Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
149
Types Of Transformers01:16

Types Of Transformers

Transformers can provide desired voltages to a circuit by modifying the number of turns in the secondary windings.
If the ratio of the number of turns in the secondary winding to that of the primary winding is greater than one, then the transformer is said to be a step-up transformer. In a step-up transformer, the voltage at the secondary winding is greater than the voltage applied at the primary winding.
However, if this ratio is less than one, the transformer is said to be a step-down...
959
Improving Translational Accuracy02:07

Improving Translational Accuracy

Base complementarity between the three base pairs of mRNA codon and the tRNA anticodon is not a failsafe mechanism. Inaccuracies can range from a single mismatch to no correct base pairing at all. The free energy difference between the correct and nearly correct base pairs can be as small as 3 kcal/ mol. With complementarity being the only proofreading step, the estimated error frequency would be one wrong amino acid in every 100 amino acids incorporated. However, error frequencies observed in...
9.7K
Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
99
The Ideal Transformer01:26

The Ideal Transformer

In single-phase two-winding transformers, two windings are coiled around a magnetic core characterized by cross-sectional area A and magnetic permeability μ. A phasor current i1 enters the left winding while i2 exits the right winding, establishing the fundamental working of the transformer through electromagnetic principles.
Ampere's Law forms the basis of understanding the magnetic field within the transformer. It states that the integral of the magnetic field intensity's...
370
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
852