Statistical analysis of parameters affecting Legionella and total cell growth in premise plumbing systems within
Marco Daniele Genuardi1, Marlies Wiegand1, Elisabeth Endres2
1Institute for the Transformation of the Energy System, West Coast University of Applied Sciences, Markt 18, 25746, Heide, Germany.
Abstract:
During the storage and distribution of water in buildings, the excessive growth of pathogens can deteriorate the quality of drinking water. This study aims to investigate the factors influencing this growth and propose technical measures for prevention. The analysis is based on an empirical data set comprising 1361 samples from 204 domestic premise plumbing systems. In 14 systems, ultrafiltration plants were installed as microbiological barriers. Legionella cultivation and flow cytometry were used to determine microbiological properties. The study identified elevated total cell counts in tapping valves and pipe end lines in numerous premise plumbing systems, indicating prolonged water stagnation prior to sampling, which facilitates microbiological growth. Higher contamination rates were observed in these systems, with peripheral taps often being contaminated in lieu of the entire system. These systems were classified as microbiologically unstable due to the relevantly higher total cell numbers at hot water taps compared to the hot water tank (>25%). Furthermore, these systems exhibited a Legionella contamination rate that was 22.3% higher than in microbiologically stable systems. In some cases, peripheral contaminations may not accurately represent the entire premise plumbing system. Increasing the discard volume during sampling from 1 L to 3-5 L could provide more precise results during standard testing. Legionella species were primarily detected in the first 1 L of water after tap activation. Additionally, statistically significant relationships were observed between direct temperature and total cell number, as well as between the presence of ultrafiltration and total cell numbers at cold water taps.
More Related Videos
08:34Legionella pneumophila Outer Membrane Vesicles: Isolation and Analysis of Their Pro-inflammatory Potential on Macrophages
Published on: February 22, 2017
12:04Microfluidic Picoliter Bioreactor for Microbial Single-cell Analysis: Fabrication, System Setup, and Operation
Published on: December 6, 2013
Related Concept Videos
Design Example: Designing a Residential Plumbing System
Single Pipe Systems
In a Type I problem, fluid properties (density and viscosity), pipe characteristics (including diameter, length, and surface roughness), and the flow rate or average velocity are...