Related Experiment Video
Updated: Jun 12, 2025

Author Spotlight: Simulation and Analysis of the Temperature Rise of Ring Main Unit Equipment
Published on: July 5, 2024
Quantitative Risk Assessment of an Oil-Gas-Hydrogen-Electricity Integrated Energy Station in China
Jianbo Zhao1, Mingkun Wu1, Hongpeng Lu1
1College of Chemistry and Chemical Engineering, Guizhou University, Guiyang 550025, Guizhou, China.
Abstract:
This paper presents a quantitative risk assessment (QRA) study of an oil-gas-hydrogen-electricity integrated energy station in China. A comprehensive assessment of the station was made in terms of consequences and risks, respectively. Consequence analysis shows that the severity of hazardous chemical leakage accidents in the station is in the order of natural gas, hydrogen, gasoline, and diesel fuel, especially in the liquefied natural gas (LNG) and compressed natural gas (CNG) storage tank areas, which may cause major accidents in the event of leakage. The results of the risk assessment showed that the individual and societal risks of the integrated oil-gas-hydrogen-electricity energy station exceeded the risk acceptance criteria. Moreover, the catastrophic rupture of LNG and CNG storage tanks is the main cause of the unacceptable risk. Additional mitigation measures for them, mainly including the installation of emergency manual shut-off valves, the installation of combustible gas detection and alarm devices, and pressure relief protection devices, can effectively reduce the risk to an acceptable level.