A LLM-Based Hybrid-Transformer Diagnosis System in Healthcare

Summary

This study introduces HybridTransNet, a novel large language model (LLM) for medical image diagnosis. This advanced AI model significantly improves brain tumor detection accuracy in healthcare informatics.

Related Concept Videos

Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
99
Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
78
Differential Relays01:20

Differential Relays

Differential relays are used to protect generators, buses, and transformers by comparing electrical quantities at different points. When a fault occurs, the difference in current between the two points triggers the relay to operate, opening the circuit breaker. Under normal conditions, the current entering (i1) and leaving (i2) a generator are equal. When a fault occurs, however, these currents become unequal, and the difference current flows in the relay operating coil, causing the relay to...
114
Reducing Line Loss01:18

Reducing Line Loss

In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss...
147
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
141
Transformers01:26

Transformers

A device that transforms voltages from one value to another using induction is called a transformer. A transformer consists of two separate coils, or windings, wrapped around the same soft iron core. However, they are electrically insulated from each other.
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
1.1K