Clustering- and statistic-based approach for detection and impact evaluation of faults in end-user substations of
Samanta A Weber1,2, Michael Fischlschweiger3, Dirk Volta4
1Energy and Life Science, University of Applied Sciences Flensburg, 24943, Flensburg, Germany. samanta.weber@hs-flensburg.de.
Abstract:
In response to climate change mitigation efforts, improving the efficiency of heat networks is becoming increasingly important. An efficient operation of energy systems depends on faultless performance. Following the need for effective fault detection and elimination methods, this study suggests a three-step workflow for increasing automation in managing defective substations on the user level within heat networks. The work focuses on a model region in northern Germany. The local heat network provides data in roughly hourly intervals, including the supply and return temperatures and the volume flow of the substations. Firstly, this study identifies common indicators of faults using k-means clustering analysis of the temperature data and expert knowledge: an exceeded return temperature level, very low cooling, and inverted temperature readings. With these indicators, the subsequent statistical identification approach confirms the successful detection of affected substations, with common diagnoses including disabled return temperature limitation units, defective motoric valves, and faults in the storage control. Lastly, the study evaluates the impact of faults on the system efficiency. Combining the temperature and the volume flow data, the workflow quantifies the negative influence of a fault, enabling the prioritization of fault elimination measures in practical application to enhance the overall system efficiency.
More Related Videos
06:45Design and Application of a Fault Detection Method Based on Adaptive Filters and Rotational Speed Estimation for an Electro-Hydrostatic Actuator
Published on: October 28, 2022
10:52Design, Instrumentation and Usage Protocols for Distributed In Situ Thermal Hot Spots Monitoring in Electric Coils using FBG Sensor Multiplexing
Published on: March 8, 2020
Related Concept Videos
Power System Three-Phase Short Circuits
Bus Impedance Matrix
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
Distribution Reliability and Automation
Fault Types
For line-to-line faults occurring between phases B and C, the...
Reclosers and Fuses
A comprehensive protection scheme for radial distribution...
Zones of Protection
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...