Studies on Shielding and Activation Levels in a Concrete-Iron-Concrete Sandwich Structure Wall in the CMUH Proton
Po-Wen Fang1, Ying-I Hsieh1, An-Cheng Shiau2
1Institute of Nuclear Engineering and Science, National Tsing Hua University, 101, Sec. 2, Kuang-Fu Road, Hsinchu, Taiwan.
Abstract:
The shielding performance and activation susceptibility of a sandwich wall in the proton therapy facility of China Medical University Hospital were investigated in an integrated manner using FLUKA Monte Carlo simulations. The 2-m-thick partition wall between two adjoining treatment rooms had a three-layered structure, which comprised a 0.2-m-thick iron layer sandwiched between two layers of 0.9-m-thick concrete. In comparison with that of a concrete wall of the same thickness, the shielding performance of the concrete-iron-concrete wall was marginally better, further reducing the transmitted dose rate by approximately a factor of 2 against secondary neutrons generated through proton bombardment. This study also investigated radioactivity levels from long-lived radionuclides ( 3 H, 22 Na, 54 Mn, 55 Fe, 60 Co, 134 Cs, 152 Eu, and 154 Eu) that are primarily induced in concrete or iron by neutrons. The specific activities of 54 Mn, 55 Fe, and 60 Co in the middle iron layer were considerably higher (by factors of 75, 25, and 5, respectively) than those in the neighboring concrete. However, as for clearance levels, the index value of the iron layer was lower than that of the neighboring concrete because of the presence of fewer types of long-lived radionuclides in iron. Under irradiation scenarios considered in this study, the residual activity levels of the sandwich wall do not exceed those of a full-concrete wall, and the indexes at various depths estimated at 5 years cooling following a 20-y operational period comply with clearance criteria.
More Related Videos
Related Concept Videos
Nuclear Power
Nuclear Fuels
Nuclear fuel consists of a fissile isotope, such as uranium-235, which must be present in sufficient quantity to provide a...
Nuclear Transmutation
Composite Masonry Walls
Masonry Cavity Walls
Maintaining a clean cavity during construction is...
Masonry Curtain Walls
Posttensioned Masonry Walls
Post-tensioned masonry walls use high-strength steel rods or flexible tendons to enhance the strength and efficiency of masonry structures. These elements are securely anchored to the foundation and extend vertically either within the cores of the masonry units or between the masonry wythes. The construction process involves building the wall with these tensioning elements in place and allowing the mortar to fully cure.
Following the curing process, the tensioning begins. Steel rods are...