EQUIVALENT STATIC WIND LOADS VS. DATABASE-ASSISTED DESIGN OF TALL BUILDINGS: AN ASSESSMENT
Sejun Park1, Emil Simiu2, DongHun Yeo3
1NIST Director's Postdoctoral Research Associate, Engineering Laboratory, National Institute of Standards and Technology, Gaithersburg, MD, USA.
Abstract:
Recent developments in pressure measurement technology, and unprecedented "big data" capabilities, have enabled the development of Database-assisted Design (DAD), a powerful innovative approach to the design of tall buildings for wind. DAD is accurate, rigorous, transparent, and user-friendly. Also, DAD eliminates unwieldy back-and-forth interactions between the wind and the structural engineer, needed in traditional practices if iterative designs are performed. In spite of these advantages, some structural engineers have shown interest in an alternative approach that uses equivalent static wind loads (ESWLs) in lieu of DAD. Such an approach is warranted if ESWLs induce in structural members demand-to-capacity indexes (DCIs) approximately equal to their peak counterparts obtained by DAD. This paper presents and assesses a simple procedure for calculating such ESWLs. The procedure uses an effective multiple points-in-time (MPIT) method for estimating combined peak wind effects, and accounts rigorously and transparently for wind directionality. A case study is presented that uses both the ESWL and DAD procedures, with the latter providing the requisite benchmark results. DCIs obtained from ESWLs based on the use of ten points-in-time (corresponding to 60 wind loading cases) were significantly closer to the benchmark DAD values than their counterparts based on the use of, e.g., four points-in-time (corresponding to 24 wind loading cases). For the building considered in this case study, ESWL-based design DCIs approximated to within approximately 3 % the DCIs yielded by DAD. The approximation was found to be poorer for cases in which a single unfavorable wind direction is strongly dominant. The ESWL procedure is generally inapplicable to structures with complex shapes. In all cases, the DAD procedure is the safest and most risk-consistent design option.
More Related Videos
Related Concept Videos
Design Example: Calculating Safe Diameter for Wind-Exposed Disc
Resultant of a General Distributed Loading
Examples such as load distribution due to wind and load distribution on a bridge illustrate how this concept is used to analyze and design safe, reliable structures under variable loading conditions. Most structures, such as residential buildings, bridges, and towers, are...
Design Consideration
The factor of safety is another key...
Design of Columns under a Centric Load
Euler's formula is applicable under the assumption that the column is a perfect, straight, homogenous prism, and it is operating...
Design of Columns under an Eccentric Load
Indeterminate Structure