This paper presents a novel computational engine based on non-recursive discrete Fourier transform (DFT) technology to detect high-resistance faults (HRFs) in power distribution networks. The non-recursive DFT approach utilizes the interconnection between a sliding window for current signals and a foundation function window during transient error. This non-recursive DFT technology is characterized by a fixed error in amplitude calculation and a rotated output angle. The proposed technique is compared against several established methods for high-resistance fault detection in distribution systems, including current reconstruction (CR) using Rogowski coils, Kalman filtering, and least-squares computational engines. The performance of each technique is evaluated by assessing the estimated percentage error in the calculation of fundamental and harmonic amplitudes. To study the proposed technique, the aforementioned methods were carefully modeled and simulated using MATLAB software for the IEEE 33-bus test feeder, simulated arcing faults, and Rogowski coils under various test conditions. The comparison is conducted under the influence of different arc models in the distribution system to assess the performance of the proposed technology. The comparative results demonstrate the effectiveness of the proposed non-recursive DFT-based technique in detecting high-resistance faults in power distribution networks, outperforming the other established methods considered in this study.
More Related Videos
10:52Design, Instrumentation and Usage Protocols for Distributed In Situ Thermal Hot Spots Monitoring in Electric Coils using FBG Sensor Multiplexing
Published on: March 8, 2020
06:04Experimental Investigation of the Hierarchical Control in DC Microgrids Using a Real-time Simulator
Published on: February 14, 2025
Related Concept Videos
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Power System Three-Phase Short Circuits
Fast Decoupled and DC Powerflow
Reclosers and Fuses
A comprehensive protection scheme for radial distribution...
Bus Impedance Matrix
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
Series R—L Circuit Transients
Using Kirchhoff's Voltage Law (KVL) to analyze this circuit helps determine the total asymmetrical fault current, which consists...