Nonunit protection based on the ratio of IVRW tangent envelope area for modular multilevel converter based HVDC grid
Yao Sun1, Yanfang Fan2, Junjie Hou3
1The School of Electrical Engineering, Xinjiang University, Xinjiang, 830017, China.
Abstract:
In modular multilevel converters-based DC power grid, short faults develop rapidly and have complex characteristics. The power electronic converter has a limited ability to withstand overcurrent. So, protection needs to quickly identify the fault area in an extremely short time. Non-unit protection based on traveling waves has the advantage of rapid action, but its ability to resist fault resistance needs to be improved. To improve protection performance, a non-unit protection based on the ratio of initial fault voltage reversal wave (IVRW) tangent envelope area is proposed. First, the waveform distortion characteristics and the waveform characteristics of the IVRW at different fault locations are analyzed. Second, the tangent envelope area ratio is used to characterize the waveform distortion characteristics, which gets rid of the influence of fault resistance. Then, a fault identification criterion is constructed. And a protection scheme based on the tangent envelope area ratio is proposed by combining the start criterion and the fault pole criterion. Simulation results show that the proposed scheme has strong resistance to fault resistance and the setting value does not depend on simulation. In addition, the scheme can still effectively identify the protection area under weak boundaries and strong noise interference.
Related Concept Videos
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Radial System Protection
In a radial system with a fault downstream of the third breaker, ideally, only the third breaker will open, isolating the fault and interrupting the load connected beyond it. The second breaker has a longer delay setting,...
Zones of Protection
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
Power System Three-Phase Short Circuits
Transformers with Off-Nominal Turns Ratios
Maximum Power Flow and Line Loadability