Drone-assisted time-varying magnetic field analysis for fault diagnosis in grounding grids
1Department of Electrical Engineering, COMSATS University Islamabd, Wah Campus, Wah, Punjab, Pakistan.
Abstract:
Grounding grids are essential for ensuring the safety of power substations, but their performance can degrade due to corrosion, fractures, or other faults. Traditional fault diagnosis methods are time-consuming, labor-intensive, and require physical access to substations, posing safety risks. This paper introduces a drone-based approach for magnetic field sensing to diagnose grounding grid faults, significantly reducing operational risks and improving efficiency. However, the movement of the drone introduces time-varying electromagnetic interference (EMI) from substation equipment and the drone itself, complicating the isolation of grounding grid signals. To address this problem, we propose a time-varying un-mixing technique combined with the Fast Independent Component Analysis (FastICA) algorithm to effectively suppress the EMI and extract the grounding grid signals. Simulation results demonstrate the efficacy of the proposed technique in separating grounding grid signals under time-varying conditions, outperforming the FastICA algorithm by 96.36% and the Independent Vector Analysis (IVA) by 41.17% at a block length of 4000 and [Formula: see text]. These results highlight the robustness and applicability of the proposed approach for real-world grounding grid fault diagnosis, ensuring accuracy and safety in EMI-rich environments. However, the performance of the proposed technique degrades at higher values of [Formula: see text], which represents the speed of the flying drone.
Related Concept Videos
Magnetostatic Boundary Conditions
Magnetic Field Due to Two Straight Wires
Magnetic Field due to Moving Charges
Consider a point charge moving with a constant velocity. Like the electric field, the magnetic field at any point is directly proportional to the magnitude of the charge and inversely proportional to the square of the distance between the source point and the field point. However, unlike the electric field, the magnetic field is always perpendicular to the plane containing the line...
Magnetic Field Due To A Thin Straight Wire
Magnetic Field Of A Current Loop
Fault Types
For line-to-line faults occurring between phases B and C, the...