Fault Location of Generator Stator with Single-Phase High-Resistance Grounding Fault Based on Signal Injection
Binghui Lei1, Yifei Wang2, Zongzhen Yang1
1Baihetan Hydropower Plant, Liangshan 615400, China.
None:
This paper proposes a novel method for locating single-phase grounding faults in generator stator windings with high resistance, which are typically challenging to locate due to weak fault characteristics. The method utilizes an active voltage injection technique combined with traveling wave reflection analysis, singular value decomposition (SVD) denoising, and discrete wavelet transform (DWT). A DC voltage signal is then injected into the stator winding, and the voltage and current signals at both terminals are collected. These signals undergo denoising using SVD, followed by DWT, to identify the arrival time of the traveling waves. Fault location is determined based on the reflection and refraction of these waves within the winding. Simulation results demonstrate that this method achieves high accuracy in fault location, even with fault resistances up to 5000 Ω. The method offers a reliable and effective solution for locating high-resistance faults in generator stator windings without requiring winding parameters, demonstrating strong potential for practical applications.
More Related Videos
10:52Design, Instrumentation and Usage Protocols for Distributed In Situ Thermal Hot Spots Monitoring in Electric Coils using FBG Sensor Multiplexing
Published on: March 8, 2020
05:11High-precision Electromagnetic Flowmeter with Empty Pipe Detection via Complex Programmable Logic Device-based Waveform Recognition
Published on: June 27, 2025
Related Concept Videos
Fault Types
For line-to-line faults occurring between phases B and C, the...
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Power System Three-Phase Short Circuits
Generation of Three-Phase Voltage
As the rotor...
Bus Impedance Matrix
In the first circuit, all machine voltage sources are short-circuited, leaving only the prefault voltage source at the fault location. The positive-sequence bus impedance matrix can be determined by solving the nodal equations,...
Series R—L Circuit Transients
Using Kirchhoff's Voltage Law (KVL) to analyze this circuit helps determine the total asymmetrical fault current, which consists...