Solar-assisted tri-generation system with LCPV‑CPC and small-scale gas turbine for year-round clean energy in hot-dry
Mohamed Bechir Ben Hamida1, Rassol Hamed Rasheed2, Narinderjit Singh Sawaran Singh3
1Deanship of Scientific Research, Imam Mohammad Ibn Saud Islamic University (IMSIU), Riyadh, Saudi Arabia.
Abstract:
This study develops, dynamically simulates, and optimizes an integrated tri‑generation system for year-round electricity, heating, and cooling supply under the hot-dry climatic conditions of Baghdad, Iraq. The proposed configuration couples a low‑concentration hybrid PV-compound parabolic concentrator (LCPV-CPC) with dual small‑scale gas turbines, high- and low-grade water-source heat pumps, and an ammonia-water absorption chiller, coordinated through a following-electric-load (FEL) strategy. The primary objectives are to maximize primary energy savings, annual cost reduction, CO2 emissions mitigation, and exergy efficiency by exploiting multi‑grade thermal integration and dispatch optimization. A methodological novelty lies in applying a Reference Vector Guided Evolutionary Algorithm (RVEA) with entropy‑weighted VIKOR analysis to achieve balanced trade‑offs among energy, economic, environmental, and thermodynamic criteria. Dynamic co‑simulation through Aspen HYSYS-MATLAB, validated against high‑quality experimental data, ensures predictive reliability. Results confirm substantial performance gains compared with a separate production facility: primary energy savings up to ~ 33%, annual cost savings exceeding 10% at favorable solar conditions, and CO2 emission reduction approaching 50%. Parametric analysis shows that increased solar irradiance significantly improves environmental and economic outcomes, with economic feasibility achieved beyond ~ 472 W/m2 average radiation. Exergy efficiency remains stable or slightly declines at high irradiance due to intensified off‑design irreversibilities. Optimal inlet water temperatures to the LCPV-CPC further enhance renewable contribution without notable thermodynamic penalties. The findings demonstrate a technically and economically viable pathway for sustainable tri‑generation in climates with strong solar resources and high cooling demand, offering a transferable optimization framework for future hybrid renewable-fossil energy applications in urban buildings.
More Related Videos
Related Concept Videos
Heat Engines
Whenever we consider heat engines (and associated devices such as refrigerators and heat pumps), we do not use the standard sign convention for heat and work. For convenience, we assume that the symbols Qh, Qc, and W represent only the amounts of heat transferred...
Generation of Three-Phase Voltage
As the rotor...
Power Factor Correction