Mitigation of inductive coupling effects on buried pipelines using gradient control conductors of overhead line
Kelthoum Hachani1, Bentouati Bachir1, Djekidel Rabah2
1Renewable Energies and Energy Management Laboratory (LMSEERGE), Engineering Materials, Energy Systems, University of Laghouat, Laghouat, Algeria.
None:
By electromagnetic perturbation effect, the extra-high voltage (EHV) overhead transmission lines can cause significant induced voltages and currents on buried metallic pipelines located in the immediate vicinity. These voltages can present a source of hazard both for the structural I ntegrity of the metallic pipeline and for the safety of personnel responsible for operation and maintenance. This paper proposes the quasi-static modeling of the electromagnetic interference to which a buried metallic pipeline will be subjected nearby an extra-high voltage (EHV) overhead transmission line, under steady-state operating conditions of the power electrical grid. Using the electrical network analysis method to evaluate the induced voltage levels and its effects on the buried pipeline; also, to propose a mitigation strategy if necessary. The results obtained show that the values of the AC induced voltage on the buried pipeline are significant and exceed the limits defined by the international NACE standard. They can cause a risk of electrocution for intervention personnel and accelerate the process of metal corrosion. Therefore, the gradient control mitigation technique of the conductors and their optimal geometric arrangement of EHV transmission line using Hippopotamus Optimization (HO) algorithm were proposed to reduce AC induced voltages within the permissible safety limits, according to the requirements of the NACE Standard. Finally, it should be noted that the implementation of these mitigation approaches have led to remarkable results in eliminating potential risks.
Related Concept Videos
Reducing Line Loss
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...
Transmission Line Design Considerations
Series Impedances: Three-Phase Line
Using Kirchhoff's laws, an integro-differential equation for the network is derived. This equation accounts for unbalanced phase currents, which may induce return currents through neutral wires and the earth, seeking the least impedance path. Earth return conductors can replace the...
Fast Decoupled and DC Powerflow
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Optimization Problems