Context-Aware Transformer GAN for Direct Generation of Attenuation and Scatter Corrected PET Data

Mojtaba Jafaritadi1, Emily Anaya2, Garry Chinn1

  • 1Department of Radiology, Stanford University, Stanford, CA 94305 USA.

Summary

This study introduces a deep learning framework using conditional generative adversarial networks (cGANs) to create corrected positron emission tomography (PET) images from uncorrected ones. The Swin-GAN model demonstrated high accuracy, enabling better image quality without transmission scans.

Related Concept Videos

Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
549
Types Of Transformers01:16

Types Of Transformers

Transformers can provide desired voltages to a circuit by modifying the number of turns in the secondary windings.
If the ratio of the number of turns in the secondary winding to that of the primary winding is greater than one, then the transformer is said to be a step-up transformer. In a step-up transformer, the voltage at the secondary winding is greater than the voltage applied at the primary winding.
However, if this ratio is less than one, the transformer is said to be a step-down...
1.7K
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
1.5K
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
635
Equivalent Circuits for Practical Transformers01:28

Equivalent Circuits for Practical Transformers

The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
1.5K
Transformers01:26

Transformers

A device that transforms voltages from one value to another using induction is called a transformer. A transformer consists of two separate coils, or windings, wrapped around the same soft iron core. However, they are electrically insulated from each other.
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
2.2K