Effects of Overload Current on the Ignition and Burning Hazards of Polyethylene-Insulated Wires
Heran Song1, Qingwen Lin1, Zhurong Dong1
1School of Automobile and Transportation Engineering, Shenzhen Polytechnic University, Shenzhen 518055, China.
Abstract:
To quantitatively elucidate the effects of overload current on the ignition and burning hazards of polyethylene-insulated wires, 2.5 mm2 polyethylene-insulated copper wires used commercially were tested in an electrical fire fault simulation system. Experiments were conducted to study the evolution of overloads, ignition, and burning. The entire process, from insulation smoking and ignition to sustained burning and final extinction driven by wire fusing, was recorded using synchronized digital and high-speed imaging. Video-based measurements were used to extract the following: smoking emission duration, ignition time, burning duration, maximum flame height, and segmented flame width. The results show that stable ignition and sustained burning occur when the overload current is greater than or equal to 180 A. As the current increases, ignition occurs earlier, while the smoking stage becomes shorter but exhibits nonmonotonic fluctuations. The burning duration shows a staged response. It first increases, then decreases toward a relatively stable level. This reflects the competition between enhanced Joule heating and accelerated wire melting and fusing. Maximum flame height and segmented flame width vary nonmonotonically with current, and the segmented flame width peaks at 200 A. A multi-indicator fire hazard evaluation framework was established and an entropy-weight TOPSIS method was applied to integrate the quantification and ranking. The overall fire hazard is greatest at 200 A. These findings provide experimental insight into overload-induced ignition and combustion behavior and contribute to a quantitative understanding of fire hazard evolution in overloaded electrical wires.
Related Concept Videos
Insulation Coordination
Household Wiring And Electrical Safety
Design Example: Automobile Ignition System
One can generate a large voltage using a car battery of 12 volts with the help of inductors. Inductors are known for opposing...
Overcurrent Relays
Instantaneous overcurrent relays activate immediately when the input current exceeds a predetermined value, known as the pickup current, instantly energizing the circuit breaker trip coil. This rapid response is vital for addressing severe faults quickly.
Time-delay overcurrent relays, on the other...
Circuit Breaker and Fuse Selection
In high-voltage systems,...
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...