A Small-Sample Fault Diagnosis Method for High-Voltage Circuit Breaker Spring Mechanisms Based on Multi-Source
Xining Li1, Hanyan Xiao1, Ke Zhao1
1State Grid Jiangsu Electric Power Research Institute, Nanjing 211103, China.
None:
To address the practical engineering challenges of limited fault samples for high-voltage circuit breaker spring operating mechanisms and the inability of single features to fully reflect equipment status, this paper proposes a small-sample fault diagnosis method based on multi-source feature fusion and Stacking ensemble learning. First, a multi-source sensing system containing MEMS (Micro-Electro-Mechanical System) pressure and travel, coil, and motor current was constructed to achieve comprehensive monitoring of the mechanical and electrical states of a 220 kV circuit breaker; in particular, the introduction of non-invasive MEMS sensors effectively solves the difficulty of capturing static spring fatigue characteristics inherent in traditional methods. Second, a high-dimensional feature space was constructed using Savitzky-Golay filtering and physical feature extraction techniques. To address the characteristics of small-sample data distribution, a two-layer Stacking ensemble learning model based on 5-fold cross-validation was designed. This model utilizes the SVM (Support Vector Machine), RF (Random Forest), and KNN (K-Nearest Neighbors) as base classifiers and Logistic Regression as the meta-learner, achieving an adaptive fusion of the advantages of heterogeneous algorithms. True-type experimental results show that the average diagnostic accuracy of this method under normal conditions and four typical fault conditions reaches 96.1%, which is superior to single base models (the RF was 94.2%). Feature importance analysis further confirms that closing and opening pressures are the most critical features for distinguishing mechanical faults. This study provides effective theoretical basis and technical support for condition-based maintenance of high-voltage circuit breakers under small-sample conditions.
Related Concept Videos
Circuit Breaker and Fuse Selection
In high-voltage systems,...
Power System Three-Phase Short Circuits
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Multi-input and Multi-variable systems
In the absence of...