Vision-Language Models for Transmission Line Fault Detection: A New Approach for Grid Reliability and Optimization
Runle Yu1, Lihao Mai2, Yang Weng2
1School of Electrical Engineering, Chongqing University, Chongqing 400044, China.
None:
Reliable fault detection along transmission corridors is essential for preventing small defects from developing into long outages and costly emergency operations. This study aims to improve the field reliability of an open vocabulary vision language backbone without retraining the large model in an end-to-end manner. The work focuses on four operational fault classes in multi-region corridor imagery collected during routine inspections and uses a Florence-2 vision language model as the base recognizer. On top of this backbone, three domain-specific components are introduced. A subclass-aware fusion scheme keeps probability mass within the active parent concept so that insulator icing and conductor icing produce stable, action-oriented decisions. A Power-Line Focus Then Crop normalization uses an attention-guided corridor window together with isotropic resizing so that thin conductors and small fittings remain visible in the processed image. A corridor geo prior reduces scores as the distance from the mapped centerline increases and in this way suppresses detections that lie outside the corridor. All methods are evaluated under a shared preprocessing and scoring pipeline in training-free and parameter-efficient tuning modes. Experiments on unseen regions show higher accuracy for skinny and low-contrast faults, fewer false alarms outside the right-of-way, and improved score calibration in the confidence range used for triage, while keeping throughput and memory usage suitable for unmanned aerial vehicles and substation edge devices.
Related Concept Videos
Fault Types
For line-to-line faults occurring between phases B and C, the...
Bewley Lattice Diagram
Transmission-Line Differential Equations
Line Section Model
A circuit representing a line section of length Δx helps in understanding the transmission line parameters. The voltage V(x) and current i(x) are measured from...
Traveling Waves: Lossless Lines
Boundary Conditions: Lossless Lines
At the receiving end, the boundary condition states that the voltage equals the product of the receiving-end impedance and current. This relationship is expressed as a function of the incident and...
Lossy Lines and Overvoltages
Attenuation
When constant series resistance and shunt conductance are present, voltage and current equations are modified. The propagation constant indicates that voltage and current waves consist of both forward and backward traveling components. These waves attenuate as they propagate, with the attenuation factor related to the resistance and conductance. In a...