M D Faiyaz Ahmed1, Md Atiqur Rahman1, Prabhu Paramasivam2
1Department of Mechanical Engineering, Vignan's Foundation for Science Technology and Research, Guntur, India.
Abstract:
This Manuscript presents an integrated Life Cycle Assessment (LCA) and Life Cycle Costing (LCC) evaluation of five 33 kV distribution designs, including three overhead (OH) lines and two underground (UG) cable systems, under typical Indian operating circumstances. All environmental and economic impacts are constantly normalized per supplied kWh during a 40-year service life, allowing for clear techno-environmental comparisons. The results show that global warming potential (GWP), fossil resource depletion and particulate matter generation are the most significant environmental effect categories. Operational I²R conductor losses are the largest contributor to lifespan impacts when analyzed per delivered electricity. This highlights the relevance of conductor resistance and loading circumstances in infrastructure planning. The comprehensive study demonstrates a clear cost-environment trade-off: underground systems have larger embodied material impacts and capital expenditure, whereas overhead systems have lower initial impacts but are still susceptible to operational loss-related consequences over time. The prevalence of operational losses is exacerbated by Indian grid emission factors and loading practices, emphasizing the significance of region-specific lifecycle normalization. The study establishes a decision-relevant paradigm for assessing 33 kV distribution infrastructure by explicitly connecting conductor design, lifespan environmental performance, and long-term cost efficiency. These insights help utilities and governments optimize medium-voltage infrastructure for ecological and economically effective power delivery.
More Related Videos
06:04Experimental Investigation of the Hierarchical Control in DC Microgrids Using a Real-time Simulator
Published on: February 14, 2025
09:26In Situ Time-dependent Dielectric Breakdown in the Transmission Electron Microscope: A Possibility to Understand the Failure Mechanism in Microelectronic Devices
Published on: June 26, 2015
Related Concept Videos
Transmission Line Design Considerations
Series Impedances: Three-Phase Line
Using Kirchhoff's laws, an integro-differential equation for the network is derived. This equation accounts for unbalanced phase currents, which may induce return currents through neutral wires and the earth, seeking the least impedance path. Earth return conductors can replace the...
Primary Distribution
Lossy Lines and Overvoltages
Attenuation
When constant series resistance and shunt conductance are present, voltage and current equations are modified. The propagation constant indicates that voltage and current waves consist of both forward and backward traveling components. These waves attenuate as they propagate, with the attenuation factor related to the resistance and conductance. In a...
Arc Length of a Curve: Problem Solving
Transmission-Line Differential Equations
Line Section Model
A circuit representing a line section of length Δx helps in understanding the transmission line parameters. The voltage V(x) and current i(x) are measured...