Differential protection scheme for transmission lines with end-of-line UPFC compensation using sequential current
Jai Prakash Sharma1, Ravi Shankar Tiwari1, Om Hari Gupta2
1Electrical Engineering Department, GLA University Mathura, Bharthia, UP, 281406, India.
None:
With the rapid growth in population, the increase in power demand has outpaced the expansion of transmission line infrastructure, often leading to overload conditions. To mitigate such challenges, Flexible AC Transmission System (FACTS) devices are widely adopted to enhance system reliability and stability. While FACTS devices significantly boost the power transfer capability of transmission lines, they can also impact the effectiveness of traditional protection relays. Among these, the Unified Power Flow Controller (UPFC) is particularly notable for its ability to regulate both active and reactive power flows independently, offering the advantages of combined series and shunt compensation. This study introduces a protection strategy based on differential current sequence components for a transmission line equipped with end-line UPFC compensation (ELUC). The proposed algorithm is validated through simulations in MATLAB Simulink and further assessed using a real-time simulator. The evaluation considers a range of scenarios including variation in fault types, fault locations, fault resistances, UPFC operating modes, simultaneous faults, and synchronization errors. The performance is thoroughly examined through real-time simulation and benchmarked against existing techniques. The results demonstrate that the proposed scheme is both selective and accurate in detecting faults under dynamic conditions.
Related Concept Videos
Transmission-Line Differential Equations
Line Section Model
A circuit representing a line section of length Δx helps in understanding the transmission line parameters. The voltage V(x) and current i(x) are measured from the...
Differential Relays
Line Protection with Impedance Relays
Under normal conditions, low load currents keep the measured...
Reclosers and Fuses
A comprehensive protection scheme for radial distribution...
Parallel RLC Circuits
A simplified parallel RLC circuit model with a DC input source generating a step response is employed in this context. When the switch is turned on, Kirchhoff's current law is applied, leading to a second-order differential equation.
Reducing Line Loss
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in...