Abstract:
This paper investigates the impact of solar and wind distributed generators on the transient stability of a 39-bus industrial power system. The system is analyzed under different configurations, including wind-only, solar-only, and hybrid DG integration. Critical Clearing Time (CCT), active power, and reactive power are used as performance metrics. The results show that DG integration improves system stability compared to the baseline case. Specifically, the CCT increases from 0.018 s (without DG) to 0.0248 s with wind DG, and up to 0.3168 s with solar DG. The hybrid configuration results in a CCT of 0.0297 s. These results indicate that solar DG provides the highest improvement in transient stability due to better voltage support characteristics. The study highlights the importance of DG type and placement in improving stability and provides insights for industrial power system design.
Related Concept Videos
Turbine-Governor Control
Wind Turbine Machine Models
Induction machines interact through the rotating magnetic field generated by the stator and the rotor. The key parameter is slip, which is the difference between synchronous speed and rotor speed relative to synchronous speed. Slip is...
Generator Voltage Control
Multimachine Stability
In analyzing the system, the nodal equations represent the relationship between bus voltages, machine voltages, and machine currents. The nodal equation is given by:
Control of Power Flow
The Swing Equation
In a steady-state operation, the mechanical torque (Τm) supplied to the generator is balanced by the electrical torque (Τe)...