Related Experiment Videos

Towards million-token context windows: a topology-preserving framework for adaptive transformer sparsification

Anderson R Santos1

  • 1Faculty of Computing, Federal University of Uberlândia (UFU), Uberlândia, Minas Gerais, Brazil. santosardr@ufu.br.

Scientific Reports
|June 22, 2026
PubMed
Summary

Reduced Interaction Sampling (RIS) is a new framework that significantly cuts computational costs in large-scale network analysis and transformer models. RIS uses stochastic sparsification to maintain accuracy while processing much longer sequences and identifying more network hubs efficiently.

Related Concept Videos

Types Of Transformers01:16

Types Of Transformers

Transformers can provide desired voltages to a circuit by modifying the number of turns in the secondary windings.
If the ratio of the number of turns in the secondary winding to that of the primary winding is greater than one, then the transformer is said to be a step-up transformer. In a step-up transformer, the voltage at the secondary winding is greater than the voltage applied at the primary winding.
However, if this ratio is less than one, the transformer is said to be a step-down...
Transformers in Distribution System01:27

Transformers in Distribution System

Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
The Ideal Transformer01:26

The Ideal Transformer

In single-phase two-winding transformers, two windings are coiled around a magnetic core characterized by cross-sectional area A and magnetic permeability μ. A phasor current i1 enters the left winding while i2 exits the right winding, establishing the fundamental working of the transformer through electromagnetic principles.
Ampere's Law forms the basis of understanding the magnetic field within the transformer. It states that the integral of the magnetic field intensity's tangential component...
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the rated...
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the copper windings...
Source Transformation01:15

Source Transformation

Source transformation is a fundamental technique employed in circuit analysis, offering a valuable tool for simplifying complex electrical circuits. This technique involves the replacement of either a voltage source in series with a resistor by a current source in parallel with a resistor, or vice versa. The key concept here is that when the original sources are deactivated (turned off), the equivalent resistance at the circuit's end terminals remains the same.
It is essential to note that when...