A Silicon-tipped Fiber-optic Sensing Platform with High Resolution and Fast Response
Published on: January 7, 2019
Performance-Enhanced Fiber-Optic Hydrogen Sensing Method Based on a Pd-Cu Alloy Microcantilever and a Reflective
Qiang Wang1, Qiongxin Wu2, Yajun Jia1
1School of Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200240, China.
Abstract:
To address the demand for early hydrogen monitoring in power equipment insulation systems, a fiber-optic Fabry-Perot (F-P) hydrogen sensor based on a Pd-Cu alloy microcantilever is proposed. The microcantilever serves as the force-sensitive structure, with a Pd-Cu alloy film deposited as the hydrogen-sensitive layer and an Au reflective layer introduced to enhance optical reflection and suppress thermal drift. Hydrogen absorption induces volume expansion of the Pd-Cu film, causing cantilever bending and a consequent variation in the F-P cavity length, which leads to a shift in the characteristic wavelength of the reflected spectrum and enables wavelength-demodulated hydrogen detection. Finite element analysis was conducted to investigate the stress distribution and displacement response, confirming the effective amplification effect of the microcantilever structure. Sensor fabrication, packaging, and hydrogen response experiments were subsequently carried out. The results show a good linear response in the hydrogen concentration range of 0-300 ppm, with a wavelength sensitivity of approximately 20.8 pm/ppm and a limit of detection of 3.24 ppm. In a 24 h stability test, the baseline fluctuation standard deviation was 22.46 pm, indicating good stability and repeatable sensing performance. Temperature variation produced a wavelength sensitivity of approximately 0.2734 nm/°C, and environmental condition tests further demonstrated stable operation under temperature, humidity, vibration, and electromagnetic disturbances. The proposed sensor exhibits immunity to electromagnetic interference, intrinsic safety, and compatibility with miniaturized integration, showing promising potential for low-concentration hydrogen monitoring in power equipment.