Determinants of Legionella spp. presence in hospital water surveillance: a five-year, three-centre study from Greece
Maria Athanasiou1, Athanasia Palaiologou1, Ioanna Chatziprodromidou1
1Department of Public Health, Epidemiology and Quality of Life, Medical School, University of Patras, Patras, Greece.
Background:
Hospital water systems are persistent reservoirs of Legionella spp. and a recognised threat to immunocompromised inpatients.
Aim:
The aim of this study was to characterise the burden and factors associated with Legionella spp. contamination across three Greek hospitals over five years.
Methods:
We retrospectively analysed 292 water samples from three acute care Greek hospitals (March 2020-April 2025), cultured by a single accredited laboratory using the methods defined in International Organization for Standardization 11731:2017. A sample was classified as positive when viable Legionella spp. were recovered at or above the laboratory limit of detection; records reported as zero counts or below the limit of detection were treated as non-detections.
Findings:
Overall, 20.9% (61/292) of samples were positive, with marked between-hospital differences: 21.2%, 35.0% and 4.4% (χ2 = 27.1, P < 10-6). Hospital 2 carried the heaviest burden (mean: 2188 colony-forming units [cfu]/L; 9.7% >10,000 cfu/L) and produced nine of the ten highest readings from hot-water taps. After adjustment, between-hospital differences remained the factor most strongly associated with detection (hospital 2 vs 3: odds ratio [OR] = 15.0, 95% confidence interval [CI]: 4.8-46.4; hospital 1 vs 3: OR = 8.6, 95% CI: 2.0-38.0; both P < 0.01). Hot-water sampling was independently associated with detection (OR = 2.76, 95% CI: 1.36-5.59, P = 0.005).
Conclusion:
Differences between these three hospitals, together with hot-water systems, were the factors most strongly associated with Legionella spp. Persistent contamination in two of three networks supports a shift from outlet-level reactive disinfection towards whole-system, risk-based water-safety planning aligned with World Health Organization and European Society of Clinical Microbiology and Infectious Diseases Study Group for Legionella Infections guidance. As a three-hospital retrospective study, these findings are preliminary and require confirmation in larger datasets.