Experimental Investigation of the Hierarchical Control in DC Microgrids Using a Real-time Simulator
Published on: February 14, 2025
Seamless grid following and grid forming inverter mode transition enabled by machine-learning based SCR estimation
Anugula Rajamallaiah1,2, Josep M Guerrero3, Yadala Pavankumar4
1School of Aeronautics and Astronautics, Zhejiang University, Hangzhou, 310027, China. arajamallaiah@zju.edu.cn.
Abstract:
The increasing penetration of inverter-based resources has led to converter-dominated power systems in which grid strength varies significantly and strongly influences inverter control performance. Grid-following (GFL) and grid-forming (GFM) control strategies offer complementary advantages; however, inappropriate mode selection or abrupt transitions between these modes can result in power oscillations, frequency deviations, and degraded stability, particularly in weak grids. Reliable real-time awareness of grid strength is therefore essential to enable seamless hybrid GFL/GFM operation. This paper proposes a control-oriented, data-driven short-circuit ratio (SCR) estimation framework to support adaptive GFL/GFM mode transitions in grid-connected inverters. A lightweight multilayer perceptron (MLP) is employed to infer grid strength directly from locally measured point-of-common-coupling voltage and current signals, without relying on explicit grid models or intrusive signal injection. The estimated SCR is used as a supervisory signal to select the appropriate operating mode, while parallel GFL and GFM controllers with internal-state synchronization ensure smooth transitions with continuity of phase angle and current references. Comprehensive simulation studies under gradual and abrupt grid-strength variations demonstrate that the proposed approach significantly improves mode-transition behavior compared with conventional ordinary least squares-based estimation. In particular, active and reactive power oscillations are reduced and frequency stability is enhanced during GFL/GFM switching. The results highlight the importance of control-enabling grid-strength estimation for reliable operation of inverter-based resources in weak and converter-dominated power systems.
Related Concept Videos
Generator Voltage Control
Simplified Synchronous Machine Model
In this model, each generator is connected to a...
Multimachine Stability
In analyzing the system, the nodal equations represent the relationship between bus voltages, machine voltages, and machine currents. The nodal equation is given by:
Fast Decoupled and DC Powerflow
Load-frequency control
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...