Microbiological evaluation of protected environments during patient occupancy
Applied Microbiology
|November 1, 1971
Summary
Laminar airflow (LAF) rooms and life island (LI) units significantly reduce microbial contamination compared to standard hospital rooms, crucial for immunocompromised cancer patients. However, LAF rooms showed persistent contamination in flooring and water systems.
Area of Science:
- Infection Control
- Environmental Microbiology
- Clinical Engineering
Background:
- Cancer chemotherapy patients are highly susceptible to infections.
- Maintaining sterile environments is critical for reducing infection risk in immunocompromised individuals.
- Conventional hospital rooms pose a higher risk of microbial exposure.
Purpose of the Study:
- To compare microbial contamination levels in different patient isolation environments.
- To assess the effectiveness of laminar airflow (LAF) rooms and life island (LI) units in controlling airborne and surface microorganisms.
- To identify sources of persistent contamination within protected environments.
Main Methods:
- Conducted microbiological monitoring in occupied LAF rooms, LI units, and regular hospital rooms.
- Sampled air for organism counts (organisms per 1,000 ft³).
- Analyzed floor samples for sterility and organism deposition rates on settling plates.
Main Results:
- LAF rooms had significantly lower organism counts (5/1,000 ft³) than LI units (31/1,000 ft³) and hospital rooms (>3,000/1,000 ft³).
- Over 70% of LAF room floor samples were sterile, contrasting with hospital rooms where none were sterile.
- LAF rooms exhibited slower organism deposition rates (1 organism/4.5 hr) compared to hospital rooms (1 organism/0.08 hr).
- Potential pathogens were more frequent in hospital room samples.
- Persistent contamination sites in LAF rooms included flooring and water supply.
- Over 50% of potential pathogens in protected units originated from the patients themselves.
Conclusions:
- LAF rooms and LI units offer superior microbial control compared to standard hospital rooms for chemotherapy patients.
- While effective, LAF rooms require attention to potential contamination sources like flooring and water systems.
- Patient-to-environment transmission is a significant factor in protected isolation units.