Inefficiency of upward displacement operating theatre ventilation
B Friberg1, S Friberg, L G Burman
1Department of Orthopedaedics, Northern University Hospital, Umeå, Sweden.
Abstract:
A new thermally based ventilation system ('Floormaster') with inlet of cool clean air at floor level, and evacuation at the ceiling of the air warmed by activity in the room (upward displacement ventilation, 17 air changes/h) was compared with a standard positive pressure (plenum) ventilation system with air supply through an inclined perforated screen along one wall at the ceiling and evacuation at floor level (conventional turbulent or mixing system, 16 air changes/h). The study was made during rigidly standardized sham operations (N = 20) performed in the same operating room by a six-member team wearing non-woven disposable or cotton clothing. In general the upward displacement system removed dust particles too small to carry bacteria (0.16-<0.3 microm, 0.001