标准化轨道绝缘测量方法的不确定性,用于流浪电流评估
Sahil Bhagat1, Jacopo Bongiorno2, Andrea Mariscotti1
1DITEN, University of Genova, 16145 Genova, Italy.
Sensors (Basel, Switzerland)
|July 14, 2023
概括
准确的轨道绝缘测试对于直流电气化运输系统至关重要. 目前用于评估轨道绝缘的标准化方法存在差异性,因此需要更可靠和灵活的测试方法.
科学领域:
- 电气工程 电气工程
- 交通基础设施 交通基础设施
背景情况:
- 在直流电气化运输系统中的流浪电流对基础设施和附近的设施构成风险.
- 有效的保护依赖于及时的维护和适当的设计,轨道绝缘评估是关键的第一步.
- 现有的标准化轨道绝缘评估方法 (EN 50122-2,IEC 62128-2) 在准确性和一致性方面存在局限性.
研究的目的:
- 批判性地分析当前轨道绝缘测试方法的变化源和实际限制.
- 评估与标准化轨道绝缘评估技术相关的不确定性.
- 倡导开发创新,更灵活,更准确的轨道绝缘评估方法.
主要方法:
- 对影响测试可变性的因素进行批判性讨论和分析.
- 在标准化轨道绝缘试验程序中评估不确定性.
- 对现有和潜在的新方法的比较评估.
主要成果:
- 确定了当前轨道绝缘测试方法的重大变化来源.
- 量化了标准化评估技术中固有的不确定性.
- 强调目前的方法不足以满足严格的新系统绝缘规格.
结论:
- 标准化轨道绝缘测试方法需要改进,因为准确性问题和变化.
- 解决测试中的不确定性对于确保可靠的基础设施保护和满足合同要求至关重要.
- 进一步研究创新和更精确的测试方法对于推进直流传输系统的安全性和效率至关重要.
相关概念视频
Insulation Coordination
171
Insulation coordination is the process of matching electric equipment's insulation strength with protective device characteristics to protect the equipment against expected overvoltages. This selection is based on engineering judgment and cost. Equipment can generally withstand short-duration high transient overvoltages, but repeated tests with identical waveforms can yield inconsistent results. As a result, standard impulse voltage waveforms are used for testing, defined by specific times...
171
Series R—L Circuit Transients
126
In a series resistor-inductor (R-L) circuit, closing the switch at the start of the time period simulates a three-phase short circuit, a fault condition where all three phases of an unloaded synchronous machine are short-circuited. When there is no fault impedance and no initial current, the initial voltage is determined by the phase angle of the source voltage.
Using Kirchhoff's Voltage Law (KVL) to analyze this circuit helps determine the total asymmetrical fault current, which consists...
Using Kirchhoff's Voltage Law (KVL) to analyze this circuit helps determine the total asymmetrical fault current, which consists...
126
Three-Phase Short Circuit—Unloaded Synchronous Machine
169
Conducting a three-phase short circuit test on an unloaded synchronous machine helps understand its impact on the system. The AC fault current's oscillogram, with the DC offset removed, reveals that the waveform amplitude decreases from an initially high value to a steady-state level for one phase of the machine.
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
169
Calculation of Self-inductance
401
The self-inductance of a circuit, often simply called the inductance, is a purely geometric factor that depends only on the circuit component's structure. More specifically, it depends on the shape and size of the component that lets the flux pass through it, thus inducing an electric field that opposes any current passing through it.
Since the effect of the induced electric field and the back EMF generated depends on the rate of change of current and the self-inductance, the inductance...
Since the effect of the induced electric field and the back EMF generated depends on the rate of change of current and the self-inductance, the inductance...
401
Potentiometer
829
Voltage and current measurements using a standard voltmeter and ammeter alter the circuit being measured either by drawing or resisting the current flow, which introduces uncertainties in the measurements. Null measurements balance the voltages so that no current flows through the measuring device and, therefore, no alterations occur in the measured circuit.
Suppose the emf of a battery needs to be measured. If the battery is directly connected to a standard voltmeter, the measured quantity is...
Suppose the emf of a battery needs to be measured. If the battery is directly connected to a standard voltmeter, the measured quantity is...
829
Resistance and Conductance
104
A conductor's DC resistance at a given temperature is influenced by its resistivity, length, and cross-sectional area. Resistivity is an inherent property of the conductor material, with annealed copper serving as the international standard for measurement. For instance, the resistivity of hard-drawn aluminum at 20 degrees Celsius is 61% of the standard conductivity of annealed copper.
Various factors impact the resistance of a conductor. Spiraling in stranded conductors increases their...
Various factors impact the resistance of a conductor. Spiraling in stranded conductors increases their...
104