通过使用测量数据验证机器学习辅助和基于电力线通信的电缆监控
Yinjia Huo1, Kevin Wang1,2, Lutz Lampe1
1Department of Electrical and Computer Engineering, The University of British Columbia, Vancouver, BC V6T 1Z4, Canada.
Sensors (Basel, Switzerland)
|January 23, 2024
概括
这项研究验证了机器学习 (ML) 用于电力线通信 (PLC) 电缆诊断,使用现实世界的数据. 拟议的方法准确地检测到电缆退化与最小的错误报警.
科学领域:
- 电气工程 电气工程
- 数据科学数据科学数据科学
- 材料科学 材料科学 材料科学
背景情况:
- 智能电网利用电力线通信 (PLC) 来实时监控电缆.
- 机器学习 (ML) 模型对机器学习辅助的电缆诊断非常有希望.
- 现有的研究往往依赖于合成数据,限制了现实世界的适用性.
研究的目的:
- 通过使用测量的PLC通道数据验证ML辅助的电缆诊断.
- 开发电源电缆的异常检测系统.
- 评估聚类和主要组件分析 (PCA) 对于电缆健康监测的有效性.
主要方法:
- 集成测量PLC通道数据与ML模型.
- 雇员集群用于数据预处理.
- 使用主要组件分析 (PCA) 来进行尺寸缩小和异常检测.
- 在健康的网络数据上训练模型,并在退化的电缆条件下进行测试.
主要成果:
- 拟议的异常检测方案在识别电缆退化方面取得了很高的准确性.
- 该系统显示了低错误报警率.
- 验证使用实验设置进行,并引入电源电缆退化.
结论:
- 使用测量PLC数据的ML辅助诊断对于电缆异常检测是有效的.
- 聚类和PCA的结合为实时电缆监控提供了一个强大的方法.
- 开发的系统为提高电网安全和维护提供了可靠的解决方案.
相关概念视频
Maximum Power Flow and Line Loadability
116
The maximum power flow for lossy transmission lines is derived using ABCD parameters in phasor form. These parameters create a matrix relationship between the sending-end and receiving-end voltages and currents, allowing the determination of the receiving-end current. This relationship facilitates calculating the complex power delivered to the receiving end, from which real and reactive power components are derived.
116
Line Loss
245
The different configurations of source-load connections include wye (star) and delta connections. The relationship between line and phase voltages and currents varies depending on the configuration. When the source is supplying power, it is transmitted through the wires to the load, and during this transmission, some power is absorbed by the wires, leading to line loss.
Line loss impacts power delivery efficiency in a balanced three-phase circuit. The symmetry in such a circuit simplifies the...
Line loss impacts power delivery efficiency in a balanced three-phase circuit. The symmetry in such a circuit simplifies the...
245
Line Protection with Impedance Relays
82
Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...
Under normal conditions, low load currents keep the measured...
82
Multimachine Stability
163
Multimachine stability analysis is crucial for understanding the dynamics and stability of power systems with multiple synchronous machines. The objective is to solve the swing equations for a network of M machines connected to an N-bus power system.
In analyzing the system, the nodal equations represent the relationship between bus voltages, machine voltages, and machine currents. The nodal equation is given by:
In analyzing the system, the nodal equations represent the relationship between bus voltages, machine voltages, and machine currents. The nodal equation is given by:
163
Three-Phase Short Circuit—Unloaded Synchronous Machine
147
Conducting a three-phase short circuit test on an unloaded synchronous machine helps understand its impact on the system. The AC fault current's oscillogram, with the DC offset removed, reveals that the waveform amplitude decreases from an initially high value to a steady-state level for one phase of the machine.
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
147
Pilot and Numeric Relaying
86
Pilot relaying is a type of differential protection used in power systems. It compares electrical quantities at the terminals of equipment via a communication channel instead of direct relay interconnection. This method is essential for transmission lines where the terminals are far apart, typically up to 80 km for lines with 69 to 115 kV ratings. Four types of communication channels are used for pilot relaying:
86