基于多相过器的高效多声源定位算法用于变压器故障

Hualiang Zhou1,2, Zhantao Su1,2, Yuxuan Huang3

  • 1NARI Group Corporation (State Grid Electric Power Research Institute), Nanjing 211106, China.

PubMed
概括

早期检测功率变压器故障至关重要. 这项研究引入了一种使用多相过器和总差异单脉冲技术的新声音定位算法,用于准确的多故障识别,改善变压器维护.

相关概念视频

Power System Three-Phase Short Circuits01:21

Power System Three-Phase Short Circuits

Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
88
Reducing Line Loss01:18

Reducing Line Loss

In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss...
154
Fault Types01:18

Fault Types

When analyzing a single line-to-ground fault from phase A to ground at a three-phase bus, it is important to consider the fault impedance. This impedance is zero for a bolted fault, equal to the arc impedance for an arcing fault, and represents the total fault impedance for a transmission-line insulator flashover. To derive sequence and phase currents, fault conditions are translated from the phase domain to the sequence domain.
For line-to-line faults occurring between phases B and C, the...
89
Three-Winding Transformers01:19

Three-Winding Transformers

Three identical single-phase transformers can be configured to form a three-phase transformer connection, which involves high-voltage and low-voltage windings. The high-voltage windings are denoted by capital letters A-B-C, while the low-voltage windings are labeled with lowercase letters a-b-c, representing their respective phases. This notation helps distinguish between the high and low voltage sides of the transformer.
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
228
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
157
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
876