带有形热量计的电源电缆的燃烧特性
1Zhengzhou Key Laboratory of Electric Power Fire Safety, College of Building Environment Engineering, Zhengzhou University of Light Industry, 450000, China.
Heliyon
|February 6, 2024
概括
这项研究研究了城市公用事业道中的四种电力电缆类型的燃烧特性. 与YJV和ZR-YJV类型相比,ZR-VV电缆显示出更低的热释放和更好的防火性能.
科学领域:
- 消防科学 消防科学 消防科学
- 材料科学 材料科学 材料科学
- 工程 工程师 工程师 工程师
背景情况:
- 电力电缆是城市公用事业道 (UUT) 中一个重要的火灾风险因素.
- 电缆绝缘,填充和覆盖非常容易发生点火.
研究的目的:
- 为了研究四种电源电缆类型 (YJV,ZR-YJV,ZR-VV,ZR-PE) 在不同的热流和外厚度下的燃烧特性.
- 分析热释放率 (HRR),有效热燃烧 (EHC),光密度指数 (ODI) 和烟雾产生率 (SPR) 对电缆点火和燃烧的影响.
主要方法:
- 使用圆热量计进行实验室实验.
- 在两种热流 (35kW/m2和75kW/m2) 和两种外厚度 (3mm和5mm) 下进行测试.
主要成果:
- 与YJV和ZR-YJV电缆相比,ZR-VV电缆的点火时间 (TTI),平均HRR和EHC都较短.
- 热流显著影响ZR-PE电缆的HRR,SPR和EHC,而外厚度的影响最小.
- 该研究确定了点火时间作为一个关键参数,取决于电缆的组成和结构.
结论:
- 与YJV和ZR-YJV相比,ZR-VV电源电缆在UUT中表现出优越的防火性能.
- 外部热流的复杂性会根据电缆特性影响燃烧行为.
- 实验室数据为消防安全评估提供了对电缆燃烧的关键见解.
更多相关视频
相关概念视频
Constant Volume Calorimetry
27.1K
Calorimeters are useful to determine the heat released or absorbed by a chemical reaction. Coffee cup calorimeters are designed to operate at constant (atmospheric) pressure and are convenient to measure heat flow (or enthalpy change) accompanying processes that occur in solution at constant pressure. A different type of calorimeter that operates at constant volume, colloquially known as a bomb calorimeter, is used to measure the energy produced by reactions that yield large amounts of heat and...
27.1K
Calorimetry
3.0K
When objects at different temperatures are placed in contact with each other but isolated from everything else, they attain thermal equilibrium. A container that prevents heat transfer in or out is called a calorimeter, and the use of a calorimeter to make measurements is called calorimetry. Generally, these measurements involve heat or specific heat capacity. The term "calorimetry problem" is used for any problem where the specified objects are thermally isolated from their...
3.0K
Constant Pressure Calorimetry
85.3K
Calorimetry is a technique used to measure the amount of heat involved in a chemical or physical process or to measure the heat transferred to or from a substance. The heat is exchanged with a calibrated and insulated device called the calorimeter. Calorimetry experiments are based on the assumption that there is no heat exchange between the insulated calorimeter and the external environment. The well-insulated calorimeters prevent the transfer of heat between the calorimeter and its external...
85.3K
Thermal expansion and Thermal stress: Problem Solving
1.2K
San Francisco's Golden Gate Bridge is exposed to temperatures ranging from -15 °C to 40 °C. At its coldest, the main span of the bridge is 1275 m long. Assuming that the bridge is made entirely of steel, what is the change in its length between these temperatures?
To solve the problem, first, identify the known and unknown quantities. The initial length (L) of the bridge is 1275 m, the coefficient of linear expansion (α) for steel is 12 x 10-6/°C, and the change in...
To solve the problem, first, identify the known and unknown quantities. The initial length (L) of the bridge is 1275 m, the coefficient of linear expansion (α) for steel is 12 x 10-6/°C, and the change in...
1.2K
Flame Photometry: Overview
596
Flame photometry, also known as flame emission spectrometry, is a technique used for the qualitative and quantitative analysis of elements present in a sample using a flame as the source of excitation energy. The concept of flame photometry was realized in the early 1860s by Kirchhoff and Bunsen, who discovered that specific elements emit characteristic radiation when excited in flames. The first instrument developed for this purpose was used to measure sodium (Na) in plant ash using a Bunsen...
596
Energy Stored In A Coaxial Cable
1.5K
A coaxial cable consists of a central copper conductor used for transmitting signals, followed by an insulator shield, a metallic braided mesh that prevents signal interference, and a plastic layer that encases the entire assembly.
In the simplest form, a coaxial cable can be represented by two long hollow concentric cylinders in which the current flows in opposite directions. The magnetic field inside and outside the coaxial cable is determined by using Ampère's law. The magnetic...
In the simplest form, a coaxial cable can be represented by two long hollow concentric cylinders in which the current flows in opposite directions. The magnetic field inside and outside the coaxial cable is determined by using Ampère's law. The magnetic...
1.5K