一个安全的双层故障保护策略,以配送网络与DERs:加强安全面对通信挑战
Wael Al Hanaineh1, Jose Matas1, Josep M Guerrero2
1Electric Engineering Department, Polytechnic University of Catalonia (EEBE-UPC), 08019 Barcelona, Spain.
Sensors (Basel, Switzerland)
|February 24, 2024
概括
这项研究引入了配电系统的双层保护系统,即使在通信故障时,也提供了强大的故障检测. 该系统通过自适应算法和本地数据处理来确保可靠的电网保护.
科学领域:
- 电气工程 电气工程
- 电力系统保护保护 电力系统保护
背景情况:
- 配送系统中的传统保护方法严重依赖通信道,使它们易受通信故障的影响.
- 当通信链路受到损害时,现有的解决方案缺乏冗余性,可能导致长时间的停电.
研究的目的:
- 为配电系统提出一种新的双层保护系统,以确保安全的故障检测和隔离,即使在通信故障期间.
- 通过提供通信独立的备份保护机制来提高电网可靠性.
主要方法:
- 第一个层采用基于总波扭曲 (THD),电压幅度估计和零序元件的自适应算法,通过通信协议协调.
- 一个二级通用集成器 (SOGI) 用于快速估计电网电压变量.
- 第二层使用局部正负序列电压组件来定位和隔离故障,在检测到通信故障时自动激活.
主要成果:
- 基于THD的第一层显示了快速故障检测,响应时间在6到8.5毫秒之间.
- 基于序列的第二层提供了大约150毫秒的备份保护响应时间.
- 在IEEE9总线系统上的模拟和实验结果验证了该系统在不同条件下检测和隔离各种故障类型的能力.
结论:
- 拟议的双层系统为配送系统提供了可靠和安全的保护方案,有效地解决了通信故障的漏洞.
- 该系统既提供了快速的初级保护,也提供了强大的通信独立的备份,大大提高了电网弹性.
相关概念视频
Zones of Protection
170
In power systems, the entire setup is divided into protective zones to isolate faults and protect the rest of the network. These zones include generators, transformers, buses, transmission lines, distribution lines, and motors. Each zone can be visualized as a separate room in a house, with each room protected by its own circuit breaker.
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
170
Reclosers and Fuses
105
Automatic circuit reclosers enhance the protection of distribution circuits by interrupting and auto-reclosing an AC circuit according to a preset sequence. They effectively manage temporary faults on overhead distribution lines, often caused by tree limbs or wildlife, by briefly disrupting service to improve overall reliability. However, contact with reclosers or energized broken conductors on the ground can pose serious hazards.
A comprehensive protection scheme for radial distribution...
A comprehensive protection scheme for radial distribution...
105
Line Protection with Impedance Relays
81
Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...
Under normal conditions, low load currents keep the measured...
81
Primary Distribution
103
Primary distribution systems deliver electrical power from substations to consumers through various voltage classes, with 15-kV class voltages being predominant among U.S. utilities. Older 2.5- and 5-kV classes are being replaced by 15-kV primaries, while higher 25- to 34.5-kV classes are used in high-density urban areas and rural regions with long feeders. Three-phase, four-wire multigrounded systems are widely employed for balanced power delivery, using the neutral wire as a grounding point.
103
Distribution Reliability and Automation
107
Distribution reliability in electrical power systems is critical for ensuring an uninterrupted power supply to consumers at minimal cost. According to IEEE Standard Terms, reliability is the probability that a device will function without failure over a specified time period or amount of usage. For electric power distribution, this translates to maintaining continuous power supply and addressing customer concerns over power outages. Several indices, as defined by IEEE Standard 1366-2012, are...
107
Secondary Distribution
85
Secondary distribution systems provide electrical energy at the utilization voltage levels from distribution transformers to customer meters. Typical secondary voltages in the United States include 120/240 V for residential use, 208Y/120 V for residential and commercial use, and 480Y/277 V for industrial and high-rise commercial use.
In residential areas, 120/240 V single-phase, three-wire service is commonly used for lighting, outlets, and large appliances. Urban areas with high-density loads...
In residential areas, 120/240 V single-phase, three-wire service is commonly used for lighting, outlets, and large appliances. Urban areas with high-density loads...
85