基于非额定频率电流注入的电流变压器的现场主动校准技术
Xin Qi1, Baoquan Wan1, Jun Zhang1
1China Electric Power Research Institute, Wuhan 430074, China.
The Review of scientific instruments
|July 10, 2024
概括
本研究引入了当前变压器 (CT) 的现场活跃校准,使得在没有电源中断的情况下能够准确测量错误. 该方法验证CT在各种电流和频率的性能,满足高精度标准.
科学领域:
- 电气工程 电气工程
- 计量学 计量学 计量学
背景情况:
- 电流变压器 (CT) 对于电力系统监控至关重要.
- 对CT的现场校准对于保持电网准确性和可靠性至关重要.
- 现有的方法通常需要断电,导致运营中断.
研究的目的:
- 为CTs开发一个活跃的现场校准方法.
- 为了使错误测量能够在没有电源中断的情况下进行.
- 在任意频率下建立CT校准的理论框架.
主要方法:
- 使用背景电流取消和非额定电流注入进行现场主动校准.
- 通过等效电路对任意频率的CT校准进行理论分析.
- 拟议的校准方法的实验验证.
主要成果:
- 精确的CT误差测量从1%到120%的额定电流,没有电源中断.
- 根据额定频率校准,在任意频率下确定相角和比率误差.
- 实验结果显示比率和相位误差的差异分别低于0.01%和1',满足0.2准确度类要求.
结论:
- 拟议的现场主动校准是评估CT性能的有效和有效工具.
- 该方法允许在非额定条件和频率下准确评估CTs.
- 该技术符合关键电力系统应用的严格准确性要求.
相关概念视频
Instrument Transformers
83
Instrument transformers, comprising voltage transformers (VTs) and current transformers (CTs), play crucial roles in power substations by providing isolated replicas of current or voltage for measurement and protection purposes. Voltage transformers reduce the primary voltage to levels suitable for relay operation and measurement, while current transformers scale down the primary current. The primary winding of a current transformer often consists of a single turn, achieved by threading the...
83
Three-Phase Short Circuit—Unloaded Synchronous Machine
135
Conducting a three-phase short circuit test on an unloaded synchronous machine helps understand its impact on the system. The AC fault current's oscillogram, with the DC offset removed, reveals that the waveform amplitude decreases from an initially high value to a steady-state level for one phase of the machine.
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
135
Overcurrent Relays
76
Overcurrent relays, crucial for circuit protection, are connected to the secondary current of a current transformer. There are two primary types of overcurrent relays: instantaneous and time-delay.
Instantaneous overcurrent relays activate immediately when the input current exceeds a predetermined value, known as the pickup current, instantly energizing the circuit breaker trip coil. This rapid response is vital for addressing severe faults quickly.
Time-delay overcurrent relays, on the other...
Instantaneous overcurrent relays activate immediately when the input current exceeds a predetermined value, known as the pickup current, instantly energizing the circuit breaker trip coil. This rapid response is vital for addressing severe faults quickly.
Time-delay overcurrent relays, on the other...
76
Power System Three-Phase Short Circuits
81
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
81
Differential Relays
125
Differential relays are used to protect generators, buses, and transformers by comparing electrical quantities at different points. When a fault occurs, the difference in current between the two points triggers the relay to operate, opening the circuit breaker. Under normal conditions, the current entering (i1) and leaving (i2) a generator are equal. When a fault occurs, however, these currents become unequal, and the difference current flows in the relay operating coil, causing the relay to...
125
Directional Relays
103
Directional relays, essential for managing unidirectional fault currents, enhance the safety and efficiency of power systems. On power lines equipped with directional relays, faults downstream (to the right) of the current transformer typically cause the fault current to lag the bus voltage by approximately 90 degrees, known as the forward direction. In contrast, upstream (left-side) faults may result in the fault current leading the bus voltage by nearly 90 degrees, termed the reverse...
103