关于长期使用±500kV复合式死角绝缘体的老化特征的研究
Zhijin Zhang1, Bingbing Wang1, Xuze Li1
1Xuefeng Mountain Energy Equipment Safety National Observation and Research Station, Chongqing University, Chongqing 400044, China.
Polymers
|July 13, 2024
概括
这项研究检查了18年的500kV复合绝缘体,发现显著的老化,特别是在高压端. 机械和电气性能下降,影响电网可靠性.
科学领域:
- 电气工程 电气工程
- 材料科学 材料科学 材料科学
- 电力系统 电力系统
背景情况:
- 复合材料绝缘体对于高压电网至关重要.
- 在高电压下长期运行加快了复合绝缘体的老化.
- 对于使用十年以上的500kV复合绝缘体的研究有限.
研究的目的:
- 研究500kV复合绝缘体的机械,电气和微观性能.
- 为了比较老旧绝缘体的性能与新旧的绝缘体和运行标准.
- 了解聚二甲基 (PDMS) 在老化复合材料绝缘体中的老化机制.
主要方法:
- 机械性能测试 (硬度,抗拉强度,延长).
- 电气性能测试 (污染闪电电压).
- 显微镜分析检查棚架结构和材料组成.
主要成果:
- 在绝缘体的高压端,老化最严重.
- 硬度符合标准,但抗拉强度和延伸度没有.
- 在潮湿条件下,污染闪电电压下降约50%.
- 显微镜分析显示了PDMS棚结构的潜在损伤和填料损失.
- 无机沉增加了硬度,但降低了疏水性.
结论:
- 陈旧的复合绝缘体在机械和电气性能上表现出显著的退化.
- 衰老机制涉及PDMS的结构损伤和物质性质变化.
- 结果为绝缘体寿命预测和高压电网运行安全提供了洞察力.
更多相关视频
相关概念视频
Insulation Coordination
127
Insulation coordination is the process of matching electric equipment's insulation strength with protective device characteristics to protect the equipment against expected overvoltages. This selection is based on engineering judgment and cost. Equipment can generally withstand short-duration high transient overvoltages, but repeated tests with identical waveforms can yield inconsistent results. As a result, standard impulse voltage waveforms are used for testing, defined by specific times...
127
Transmission Line Design Considerations
133
Aluminum has become the material of choice for overhead transmission lines, surpassing copper due to its abundance and cost-effectiveness. The most prevalent type is the aluminum conductor, steel-reinforced (ACSR), which combines aluminum strands around a steel core. Other variants include all-aluminum conductors (AAC), all-aluminum alloy conductors (AAAC), aluminum conductor alloy-reinforced (ACAR), and aluminum-clad steel conductors. Advanced designs, such as aluminum conductors with steel...
133
Cable Subjected to Concentrated Loads
817
Flexible cables are commonly used in various applications for support and load transmission. Consider a cable fixed at two points and subjected to multiple vertically concentrated loads. Determine the shape of the cable and the tension in each portion of the cable, given the horizontal distances between the loads and supports.
817
Three-Phase Short Circuit—Unloaded Synchronous Machine
135
Conducting a three-phase short circuit test on an unloaded synchronous machine helps understand its impact on the system. The AC fault current's oscillogram, with the DC offset removed, reveals that the waveform amplitude decreases from an initially high value to a steady-state level for one phase of the machine.
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
135
Capacitor With A Dielectric
3.9K
Parallel plate capacitors consist of two conducting plates separated by a certain distance. However, it is mechanically difficult to hold the large plates parallel to each other without actual contact. Hence, a dielectric layer is commonly placed between the plates, which provides an easy solution for holding the plates together with a small gap and increases the capacitance of the capacitor.
Dielectrics are non-conducting materials with no free or loosely bound electrons. When a dielectric is...
Dielectrics are non-conducting materials with no free or loosely bound electrons. When a dielectric is...
3.9K
Power System Three-Phase Short Circuits
81
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
81