在渐进式短路冲动下为10kV-400kVA 3D伤口芯变压器的分布式振动监测系统
Jiagui Tao1, Sicong Zhang1, Jianzhuo Dai1
1Electrical Power Academy of Sciences, State Grid of Jiangsu Electric Power Co., Ltd., Nanjing 210024, China.
Sensors (Basel, Switzerland)
|July 13, 2024
概括
在短路冲动下测试变压器绕线对于有效的电力分配至关重要. 增加的电流显著影响绕应力和变形,需要先进的监测系统来确保电网可靠性.
科学领域:
- 电气工程 电气工程
- 电力系统工程 电力系统工程
背景情况:
- 高效的配电变压器越来越多地集成到电网中.
- 评估它们的抗短路能力对于电网稳定性至关重要.
研究的目的:
- 调查短路冲动对高效功率变压器的绕线变形的影响.
- 在各种短路条件下分析内部力和变形.
主要方法:
- 一个有限元理论模型的三相三线3D伤口核心变压器被开发.
- 模拟是在逐渐增加的短路冲击脉冲 (60%至120%) 下进行的.
- 分析了内部等效力和总变形分布.
主要成果:
- 对于等效应力和总变形的变化率在短路电流的60%到80%之间达到顶峰.
- 应力和变形的最大变化率达到了大约177-178%.
- 在120%电流下,最大等效应力为29.81MPa,总变形为38.70μm.
结论:
- 短路电流显著影响变压器线圈的完整性.
- 建议使用无线传感器的分布式监控系统进行实时振动分析.
- 该系统补充了传统的高效电网随机检查方法.
相关概念视频
Instrument Transformers
83
Instrument transformers, comprising voltage transformers (VTs) and current transformers (CTs), play crucial roles in power substations by providing isolated replicas of current or voltage for measurement and protection purposes. Voltage transformers reduce the primary voltage to levels suitable for relay operation and measurement, while current transformers scale down the primary current. The primary winding of a current transformer often consists of a single turn, achieved by threading the...
83
Power System Three-Phase Short Circuits
81
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
81
Three-Phase Short Circuit—Unloaded Synchronous Machine
135
Conducting a three-phase short circuit test on an unloaded synchronous machine helps understand its impact on the system. The AC fault current's oscillogram, with the DC offset removed, reveals that the waveform amplitude decreases from an initially high value to a steady-state level for one phase of the machine.
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
135
Transformers in Distribution System
100
Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
100
Three-Winding Transformers
221
Three identical single-phase transformers can be configured to form a three-phase transformer connection, which involves high-voltage and low-voltage windings. The high-voltage windings are denoted by capital letters A-B-C, while the low-voltage windings are labeled with lowercase letters a-b-c, representing their respective phases. This notation helps distinguish between the high and low voltage sides of the transformer.
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
221
Insulation Coordination
127
Insulation coordination is the process of matching electric equipment's insulation strength with protective device characteristics to protect the equipment against expected overvoltages. This selection is based on engineering judgment and cost. Equipment can generally withstand short-duration high transient overvoltages, but repeated tests with identical waveforms can yield inconsistent results. As a result, standard impulse voltage waveforms are used for testing, defined by specific times...
127