.

Yuefeng Hao1, Zhanlong Zhang1, Xueli Liu1,2

  • 1School of Electrical Engineering, Chongqing University, Chongqing 400044, China.

PubMed
概括

准确预测变压器绕热点温度对于故障预测至关重要. 本研究介绍了一种自注意门反复单元 (SA-GRU) 模型,该模型可以考虑数据滞后,提高反转精度并降低模型复杂性.

相关概念视频

Three-Winding Transformers01:19

Three-Winding Transformers

Three identical single-phase transformers can be configured to form a three-phase transformer connection, which involves high-voltage and low-voltage windings. The high-voltage windings are denoted by capital letters A-B-C, while the low-voltage windings are labeled with lowercase letters a-b-c, representing their respective phases. This notation helps distinguish between the high and low voltage sides of the transformer.
In the per-unit equivalent circuit of a grounded Y-Y three-phase...
217
Equivalent Circuits for Practical Transformers01:28

Equivalent Circuits for Practical Transformers

The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
406
Transformers01:26

Transformers

A device that transforms voltages from one value to another using induction is called a transformer. A transformer consists of two separate coils, or windings, wrapped around the same soft iron core. However, they are electrically insulated from each other.
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
1.1K
Transformers with Off-Nominal Turns Ratios01:25

Transformers with Off-Nominal Turns Ratios

In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
149
Energy Losses in Transformers01:21

Energy Losses in Transformers

In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality,  the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be  the high resistance of the...
852
Node Analysis for AC Circuits01:14

Node Analysis for AC Circuits

Consider an angioplasty system featuring a catheter equipped with a turbine, a critical tool for removing plaque deposits from coronary arteries. This intricate medical device operates using a circuit model reminiscent of a dual-node RLC circuit powered by a current-controlled voltage source.
To unravel the complexities of this system, nodal analysis is employed, a powerful technique founded on Kirchhoff's current law (KCL), which remains valid for phasors. AC circuits can effectively be...
306