基于真空断路器的通用HVDC-HVAC断路器的概念设计
Fady Wadie1, Tamer Eliyan2,3
1Mechatronics and Robotics Engineering Department, Faculty of Engineering, Egyptian Russian University, Badr City, Egypt. engfadywadie@hotmail.com.
Scientific reports
|August 27, 2024
概括
引入了一种全新的通用高压断路器 (UHVCB) 概念,简化了高压直流 (HVDC) 和高压交流电 (HVAC) 系统的生产和降低成本. 这一创新为电力传输断路器带来了更经济,更高效的未来.
科学领域:
- 电气工程 电气工程
- 电力系统工程 电力系统工程
背景情况:
- 现代电力系统需要不同的高压断路器 (HVAC-CB和HVDC-CB),需要单独的生产线,增加制造复杂性和成本.
- 这种双重要求导致了更高的成本和更复杂的断路器制造过程.
研究的目的:
- 为通用高压断路器 (UHVCB) 提出一个概念设计,适用于高压直流 (HVDC) 和高压交流 (HVAC) 系统.
- 为两种传输系统展示单一断路器设计的可行性和好处,旨在实现更快,更简单,更经济的生产.
主要方法:
- 拟议的UHVCB设计是基于现有的HVDC-CB设计,采用L-C变频分支.
- 在HVAC和HVDC传输系统中,HVCB经过了严格的测试,以评估其性能.
- 为了优化性能,研究了L-C分支的参数变化 (L: 0.3-1 mH,C: 10-30 μF).
主要成果:
- 在HVAC和HVDC传输系统中,HVCB表现出可靠的性能.
- 与传统的HVCB相比,HVCB的使用显著降低了短暂恢复电压 (TRV) 从750kV降至430kV.
- 测试包括技术性能和经济可行性评估.
结论:
- 一个适合HVDC和HVAC系统的通用高压断路器 (UHVCB) 是可以实现的.
- 这一初步步骤为更经济和精简的断路器制造铺平了道路,使整个电力行业受益.
相关概念视频
Circuit Breaker and Fuse Selection
98
A circuit breaker is a device engineered to interrupt fault currents and sometimes reclose automatically. When a fault current is detected, the breaker separates the electrical contacts, which generates an arc. This arc is extinguished by methods such as elongation, cooling, or splitting, depending on the breaker's design. Breakers are categorized based on the voltage they operate at and the medium used for arc extinction, such as air, oil, SF6 gas, or vacuum.
In high-voltage systems,...
In high-voltage systems,...
98
Power System Three-Phase Short Circuits
78
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
78
Voltage Doubler Circuit
505
A voltage doubler circuit integrates two main components: a clamping section and a rectifier section. The clamping section consists of a capacitor (C1) and a diode (D1), whereas the rectifier section is equipped with another diode (D2) and capacitor (C2). This circuit produces an output voltage with twice the amplitude of the sinusoidal input voltage.
505
Reclosers and Fuses
99
Automatic circuit reclosers enhance the protection of distribution circuits by interrupting and auto-reclosing an AC circuit according to a preset sequence. They effectively manage temporary faults on overhead distribution lines, often caused by tree limbs or wildlife, by briefly disrupting service to improve overall reliability. However, contact with reclosers or energized broken conductors on the ground can pose serious hazards.
A comprehensive protection scheme for radial distribution...
A comprehensive protection scheme for radial distribution...
99
Three-Phase Short Circuit—Unloaded Synchronous Machine
133
Conducting a three-phase short circuit test on an unloaded synchronous machine helps understand its impact on the system. The AC fault current's oscillogram, with the DC offset removed, reveals that the waveform amplitude decreases from an initially high value to a steady-state level for one phase of the machine.
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
133
Three-Phase Circuits
394
AC power distribution systems have three categories: single-phase, two-phase, and three-phase systems. The single-phase circuit, common in residential settings, typically employs a two-wire system connecting a single AC source to various loads. These circuits support standard household appliances operating at 120 volts (V) and 240 V, such as lamps, televisions, and microwaves. The first generators, Niagara Falls hydro plant installed in 1895, were two-phase and designed by Nikola Tesla. The...
394