使用闪电,承受电压测试和有限元分析在干净和污染环境中使用不同配置的高压磁盘绝缘器的性能分析
Arfan Ali1,2, Abdul Rauf Bhatti1, Akhtar Rasool3
1Department of Electrical Engineering and Technology, Government College University, Faisalabad, 38000, Pakistan.
Scientific reports
|August 31, 2024
概括
交替的棚隔热器显著减少了高压电力系统的污染闪现. 这些设计在受污染的环境中提供了卓越的性能,提高了电力系统的安全性和可靠性.
科学领域:
- 电气工程 电气工程
- 材料科学 材料科学 材料科学
背景情况:
- 高压绝缘体上污染引起的闪电威胁到电力系统的安全性.
- 绝缘体故障是巴基斯坦等污染地区的关键问题.
研究的目的:
- 调查绝缘体形状对减少污染闪过的影响.
- 为了比较深层下肋和交替棚隔热器设计的性能.
主要方法:
- 根据IEC标准60383.3,测试两个绝缘体设计 (深深的下肋和交替的棚)
- 在COMSOL Multiphysics®中使用有限元法模拟绝缘体性能.
- 在干净和污染条件下分析电场和电位分布.
主要成果:
- 相比于深深的肋下绝缘体,交替棚式绝缘体在干净条件下显示了25.377%的高闪电压,在污染条件下显示了27.400%的高闪电压.
- 深深的肋下绝缘器显示闪电电压降低了5.008%,而交替的棚式绝缘器显示污染条件下降了3.233%.
- 有限元法分析验证了实验结果,显示了由于污染层造成的电场峰值.
结论:
- 交替的棚隔热器在减轻污染闪现方面表现出卓越的性能.
- 这些发现对于提高污染环境中的电力系统的安全性和可靠性至关重要.
- 绝缘体设计在防止闪电和确保电网稳定性方面发挥着至关重要的作用.
相关概念视频
Insulation Coordination
125
Insulation coordination is the process of matching electric equipment's insulation strength with protective device characteristics to protect the equipment against expected overvoltages. This selection is based on engineering judgment and cost. Equipment can generally withstand short-duration high transient overvoltages, but repeated tests with identical waveforms can yield inconsistent results. As a result, standard impulse voltage waveforms are used for testing, defined by specific times...
125
Design Example: Calculating Safe Diameter for Wind-Exposed Disc
46
Assessing safety in wind-exposed installations is crucial to preventing potential failures. This example explores the calculation and design adjustments needed to mount a circular disc on a building facade, where wind forces are a primary concern. A 4-meter diameter disc was initially designed as an aesthetic feature facing winds at a velocity of 25 meters per second, with an air density of 1.25 kilograms per cubic meter. Given these conditions, the drag force on the disc was determined using...
46
Transmission Line Design Considerations
131
Aluminum has become the material of choice for overhead transmission lines, surpassing copper due to its abundance and cost-effectiveness. The most prevalent type is the aluminum conductor, steel-reinforced (ACSR), which combines aluminum strands around a steel core. Other variants include all-aluminum conductors (AAC), all-aluminum alloy conductors (AAAC), aluminum conductor alloy-reinforced (ACAR), and aluminum-clad steel conductors. Advanced designs, such as aluminum conductors with steel...
131
Three-Phase Short Circuit—Unloaded Synchronous Machine
132
Conducting a three-phase short circuit test on an unloaded synchronous machine helps understand its impact on the system. The AC fault current's oscillogram, with the DC offset removed, reveals that the waveform amplitude decreases from an initially high value to a steady-state level for one phase of the machine.
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
132
Power System Three-Phase Short Circuits
78
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
78
Circuit Breaker and Fuse Selection
96
A circuit breaker is a device engineered to interrupt fault currents and sometimes reclose automatically. When a fault current is detected, the breaker separates the electrical contacts, which generates an arc. This arc is extinguished by methods such as elongation, cooling, or splitting, depending on the breaker's design. Breakers are categorized based on the voltage they operate at and the medium used for arc extinction, such as air, oil, SF6 gas, or vacuum.
In high-voltage systems,...
In high-voltage systems,...
96