在功率能源系统中最佳协调定向超电流继电器,强调变量的离散性:全面比较

Aram Bayazidi1, Ali Abdali2,3, Juan C Vasquez4

  • 1Faculty of Electrical and Computer Engineering, University of Tabriz, Tabriz, Iran.

Heliyon
|October 14, 2024
PubMed
概括

本研究介绍了一种高探索粒子群集优化 (HEPSO) 算法,以优化循环电源网络中的超电流继电器协调,确保没有错误的协调. 与标准测试系统上的其他方法相比,HEPSO算法表现出卓越的性能.

相关概念视频

Directional Relays01:25

Directional Relays

Directional relays, essential for managing unidirectional fault currents, enhance the safety and efficiency of power systems. On power lines equipped with directional relays, faults downstream (to the right) of the current transformer typically cause the fault current to lag the bus voltage by approximately 90 degrees, known as the forward direction. In contrast, upstream (left-side) faults may result in the fault current leading the bus voltage by nearly 90 degrees, termed the reverse...
94
Line Protection with Impedance Relays01:27

Line Protection with Impedance Relays

Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...
68
Overcurrent Relays01:26

Overcurrent Relays

Overcurrent relays, crucial for circuit protection, are connected to the secondary current of a current transformer. There are two primary types of overcurrent relays: instantaneous and time-delay.
Instantaneous overcurrent relays activate immediately when the input current exceeds a predetermined value, known as the pickup current, instantly energizing the circuit breaker trip coil. This rapid response is vital for addressing severe faults quickly.
Time-delay overcurrent relays, on the other...
71
Reclosers and Fuses01:26

Reclosers and Fuses

Automatic circuit reclosers enhance the protection of distribution circuits by interrupting and auto-reclosing an AC circuit according to a preset sequence. They effectively manage temporary faults on overhead distribution lines, often caused by tree limbs or wildlife, by briefly disrupting service to improve overall reliability. However, contact with reclosers or energized broken conductors on the ground can pose serious hazards.
A comprehensive protection scheme for radial distribution...
88
Radial System Protection01:23

Radial System Protection

Radial systems employ time-delay overcurrent relays to reduce load interruptions. When a fault occurs, the nearest breaker opens first, while upstream breakers remain closed due to longer delay settings. This approach ensures minimal disruption to the rest of the system.
In a radial system with a fault downstream of the third breaker, ideally, only the third breaker will open, isolating the fault and interrupting the load connected beyond it. The second breaker has a longer delay setting,...
91
Differential Relays01:20

Differential Relays

Differential relays are used to protect generators, buses, and transformers by comparing electrical quantities at different points. When a fault occurs, the difference in current between the two points triggers the relay to operate, opening the circuit breaker. Under normal conditions, the current entering (i1) and leaving (i2) a generator are equal. When a fault occurs, however, these currents become unequal, and the difference current flows in the relay operating coil, causing the relay to...
114