一个通用的高压SF6断路器用于HVDC和HVAC系统
Fady Wadie1, Tamer Eliyan2,3
1Mechatronics and Robotics Engineering Department, Faculty of Engineering, Egyptian Russian University, Badr City, Egypt. fady-wadie@eru.edu.eg.
Scientific reports
|January 8, 2025
概括
一种全新的通用高压断路器 (UHAD-CB) 集成了交流和直流系统,降低了制造成本和复杂性. 这种创新的设计提高了性能,为输电行业带来了显著的好处.
科学领域:
- 电气工程 电气工程
- 电力系统工程 电力系统工程
- 材料科学 材料科学 材料科学
背景情况:
- 高压交流电 (HVAC) 和高压直流 (HVDC) 传输系统依赖于专门的断路器 (CB).
- 单独的HVAC-CB和HVDC-CB生产线增加了制造商的生产时间和成本.
- 需要一个统一的解决方案来简化生产并降低整个行业的开支.
研究的目的:
- 提出一个通用高压断路器 (UHAD-CB),适用于HVAC和HVDC系统.
- 降低电力传输行业的制造负担和总体成本.
- 评估拟议的UHAD-CB在各种电网应用中的性能和可靠性.
主要方法:
- 基于HVDC-CB结构的通用断路器 (UHAD-CB) 的开发.
- 在SF6断路器设计中集成一个变速器L-C分支.
- 在HVDC和HVAC传输系统中测试和评估UHAD-CB的性能.
主要成果:
- 在HVDC和HVAC运行环境中,UHAD-CB表现出可靠性和有效性.
- 与传统的HVAC-CB相比,暂时恢复电压下降了28%.
- 优化的L和C值分别为0.1mH和50μF.
结论:
- 拟议的UHAD-CB成功地集成了HVAC和HVDC系统的功能.
- 该设计提供了更好的性能,降低了制造成本和运营效率.
- 这一创新为电力传输行业带来了重大进步.
相关概念视频
Circuit Breaker and Fuse Selection
87
A circuit breaker is a device engineered to interrupt fault currents and sometimes reclose automatically. When a fault current is detected, the breaker separates the electrical contacts, which generates an arc. This arc is extinguished by methods such as elongation, cooling, or splitting, depending on the breaker's design. Breakers are categorized based on the voltage they operate at and the medium used for arc extinction, such as air, oil, SF6 gas, or vacuum.
In high-voltage systems,...
In high-voltage systems,...
87
Reclosers and Fuses
83
Automatic circuit reclosers enhance the protection of distribution circuits by interrupting and auto-reclosing an AC circuit according to a preset sequence. They effectively manage temporary faults on overhead distribution lines, often caused by tree limbs or wildlife, by briefly disrupting service to improve overall reliability. However, contact with reclosers or energized broken conductors on the ground can pose serious hazards.
A comprehensive protection scheme for radial distribution...
A comprehensive protection scheme for radial distribution...
83
Insulation Coordination
113
Insulation coordination is the process of matching electric equipment's insulation strength with protective device characteristics to protect the equipment against expected overvoltages. This selection is based on engineering judgment and cost. Equipment can generally withstand short-duration high transient overvoltages, but repeated tests with identical waveforms can yield inconsistent results. As a result, standard impulse voltage waveforms are used for testing, defined by specific times...
113
Voltage Doubler Circuit
465
A voltage doubler circuit integrates two main components: a clamping section and a rectifier section. The clamping section consists of a capacitor (C1) and a diode (D1), whereas the rectifier section is equipped with another diode (D2) and capacitor (C2). This circuit produces an output voltage with twice the amplitude of the sinusoidal input voltage.
465
Primary Distribution
96
Primary distribution systems deliver electrical power from substations to consumers through various voltage classes, with 15-kV class voltages being predominant among U.S. utilities. Older 2.5- and 5-kV classes are being replaced by 15-kV primaries, while higher 25- to 34.5-kV classes are used in high-density urban areas and rural regions with long feeders. Three-phase, four-wire multigrounded systems are widely employed for balanced power delivery, using the neutral wire as a grounding point.
96
Power System Three-Phase Short Circuits
75
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
75