电力变压器的增强保护方案集成阿尔法平面分析
Ahmed S Sayed1, Ehab M Nabil2, Almoataz Y Abdelaziz1,3
1Electrical Power and Machines Department, Faculty of Engineering, Ain Shams University, Cairo, 11517, Egypt.
Scientific reports
|March 14, 2025
概括
这项研究使用阿尔法平面 (AP) 概念增强了变压器保护,提高了对故障的可靠性. 这种新方法比传统的百分差 (PD) 保护提供了更好的灵敏度和更快的触发速度.
科学领域:
- 电气工程 电气工程
- 电力系统工程 电力系统工程
背景情况:
- 功率变压器对于电力系统至关重要,需要可靠的保护.
- 传统的百分差 (PD) 保护面临诸如电流变压器 (CT) 和和检测某些故障等挑战.
研究的目的:
- 通过整合alpha平面 (AP) 概念,提出一个增强的变压器保护方案.
- 为了提高变压器差异保护的灵敏度,稳定性和速度.
主要方法:
- 根据变压器电流的行为重新定义AP限制和操作区域.
- 开发一种新的算法来计算α平面复合比.
- 使用 MATLAB/SIMULINK 和实验测试评估拟议的方案和 PD 方法.
主要成果:
- 拟议的基于AP的方案显示了对高阻抗地面故障的更高灵敏度.
- 它在外部故障下在CT和期间保持稳定性.
- 该方案与传统的PD方法相比,提供更快的触发时间.
结论:
- 集成AP概念为变压器保护提供了强大的解决方案.
- 这种增强的方案克服了传统PD保护的局限性.
- 它确保了网络稳定性和可靠性的提高.
相关概念视频
Zones of Protection
122
In power systems, the entire setup is divided into protective zones to isolate faults and protect the rest of the network. These zones include generators, transformers, buses, transmission lines, distribution lines, and motors. Each zone can be visualized as a separate room in a house, with each room protected by its own circuit breaker.
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
122
Power System Three-Phase Short Circuits
71
Determining the subtransient fault current in a power system involves representing transformers by their leakage reactances, transmission lines by their equivalent series reactances, and synchronous machines as constant voltage sources behind their subtransient reactances. In this analysis, certain elements are excluded, such as winding resistances, series resistances, shunt admittances, delta-Y phase shifts, armature resistance, saturation, saliency, non-rotating impedance loads, and small...
71
Reducing Line Loss
141
In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss...
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss...
141
Differential Relays
94
Differential relays are used to protect generators, buses, and transformers by comparing electrical quantities at different points. When a fault occurs, the difference in current between the two points triggers the relay to operate, opening the circuit breaker. Under normal conditions, the current entering (i1) and leaving (i2) a generator are equal. When a fault occurs, however, these currents become unequal, and the difference current flows in the relay operating coil, causing the relay to...
94
Transformers in Distribution System
98
Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
98
Instrument Transformers
63
Instrument transformers, comprising voltage transformers (VTs) and current transformers (CTs), play crucial roles in power substations by providing isolated replicas of current or voltage for measurement and protection purposes. Voltage transformers reduce the primary voltage to levels suitable for relay operation and measurement, while current transformers scale down the primary current. The primary winding of a current transformer often consists of a single turn, achieved by threading the...
63