变压器树脂在不同条件下的介电性质:对仪器变压器稳定性和精度的影响
Simone Vincenzo Suraci1, Jizhu Jin1, Roberto Tinarelli1
1Department of Electrical, Electronic, and Information Engineering (DEI), University of Bologna, 40136 Bologna, Italy.
Sensors (Basel, Switzerland)
|March 17, 2025
概括
仪器变压器 (IT) 的精度取决于树脂的特性. 这项研究表明,树脂变化和老化显著影响IT性能,强调需要仔细选择材料以确保可靠的电气测量.
科学领域:
- 电气工程 电气工程
- 材料科学 材料科学 材料科学
背景情况:
- 仪表变压器 (IT) 对于精确的电测量至关重要.
- 由于环境条件和电磁场等操作因素,IT性能下降.
- 在现场验证IT准确性是很困难的,需要在安装前了解性能.
研究的目的:
- 为了研究树脂性能变化对仪表变压器精度的影响.
- 评估不同环境条件下的老化如何影响IT性能.
主要方法:
- 准备的树脂样本具有不同的固化温度.
- 进行的老化试验,包括暴露于温度和温度-湿度的组合.
- 在老化过程中测量样品的介电性质.
- 评估了介电变化对IT准确性的影响.
主要成果:
- 树脂的特性显著影响IT准确性.
- 老化测试显示了介电性质的变化,与精度偏差相关.
- 温度和湿度等环境因素加剧了树脂变化的影响.
结论:
- 选择合适的树脂特性对于确保可靠的仪表变压器性能至关重要.
- 错误的树脂选择可能会导致IT准确性的重大偏差.
- 了解树脂-过电性质关系是预测和保持IT准确性的关键.
相关概念视频
Instrument Transformers
63
Instrument transformers, comprising voltage transformers (VTs) and current transformers (CTs), play crucial roles in power substations by providing isolated replicas of current or voltage for measurement and protection purposes. Voltage transformers reduce the primary voltage to levels suitable for relay operation and measurement, while current transformers scale down the primary current. The primary winding of a current transformer often consists of a single turn, achieved by threading the...
63
Energy Losses in Transformers
818
In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality, the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
818
Equivalent Circuits for Practical Transformers
373
The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
373
Transformers in Distribution System
98
Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
98
Insulation Coordination
104
Insulation coordination is the process of matching electric equipment's insulation strength with protective device characteristics to protect the equipment against expected overvoltages. This selection is based on engineering judgment and cost. Equipment can generally withstand short-duration high transient overvoltages, but repeated tests with identical waveforms can yield inconsistent results. As a result, standard impulse voltage waveforms are used for testing, defined by specific times...
104
Transformers
1.0K
A device that transforms voltages from one value to another using induction is called a transformer. A transformer consists of two separate coils, or windings, wrapped around the same soft iron core. However, they are electrically insulated from each other.
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...
1.0K