对挑战的全面分析和两种实际方法,用于保护连接到基于DFIG的风电场的输电线路中的远距离继电器的协调
Reza Shahbazzadeh1, Mehrdad Tarafdar Hagh2,3, Reza Ghanizadeh1
1Department of Electrical Engineering, Urmia Branch, Islamic Azad University, Urmia, Iran.
Scientific reports
|May 19, 2025
概括
新的保护方法改善了电力系统中双输电感应发电机 (DFIG) 的距离继电器协调. 这些解决方案可以防止风电场在故障期间断开连接,确保电网稳定性和符合电网规范.
科学领域:
- 电气工程 电气工程
- 电力系统保护保护 电力系统保护
- 整合可再生能源的整合
背景情况:
- 双输电感应发电机 (DFIG) 越来越多地集成到高压电力系统中.
- 由于DFIG的行为,特别是断路时杆电路的激活,挑战了距离保护继电器的准确性.
- 错误的阻抗估计可能导致故障操作和不必要的风电场断开连接,与电网代码要求相冲突.
研究的目的:
- 为了应对DFIG风电场的远程保护协调方面的挑战.
- 提出创新方法,防止风力发电场在故障条件下错误触发.
- 通过高可再生能源透来提高电力系统保护的可靠性.
主要方法:
- 一种时间协调方法,涉及到连接到风电场的输电线路继电器的小延迟.
- 一种混合方法,将时间延迟与低带宽阻断信号相结合,以提高可靠性.
- 使用模拟和性能分析进行全面评估.
主要成果:
- 提出的方法有效地防止在故障条件下远距离继电器的故障.
- 由DFIG杆激活引起的不正确阻抗估计问题得到缓解.
- 证明了保护系统的可靠性和性能的提高.
结论:
- 开发的保护策略为在具有显著DFIG透的电力系统中协调距离继电器提供了实用解决方案.
- 这些方法确保风力发电场在干扰期间的连接持续,与电网规范的要求保持一致.
- 该研究有助于提高电网的稳定性和可靠性,并整合可再生能源.
相关概念视频
Line Protection with Impedance Relays
62
Coordinating time-delay overcurrent relays in complex radial systems and directional overcurrent relays in multi-source transmission loops can be challenging. Impedance relays address these issues by responding to the voltage-to-current ratio, specifically measuring the apparent impedance of a line. These relays become more sensitive during faults as current increases and voltage decreases, thereby reducing the apparent impedance.
Under normal conditions, low load currents keep the measured...
Under normal conditions, low load currents keep the measured...
62
Reclosers and Fuses
78
Automatic circuit reclosers enhance the protection of distribution circuits by interrupting and auto-reclosing an AC circuit according to a preset sequence. They effectively manage temporary faults on overhead distribution lines, often caused by tree limbs or wildlife, by briefly disrupting service to improve overall reliability. However, contact with reclosers or energized broken conductors on the ground can pose serious hazards.
A comprehensive protection scheme for radial distribution...
A comprehensive protection scheme for radial distribution...
78
Differential Relays
94
Differential relays are used to protect generators, buses, and transformers by comparing electrical quantities at different points. When a fault occurs, the difference in current between the two points triggers the relay to operate, opening the circuit breaker. Under normal conditions, the current entering (i1) and leaving (i2) a generator are equal. When a fault occurs, however, these currents become unequal, and the difference current flows in the relay operating coil, causing the relay to...
94
Directional Relays
85
Directional relays, essential for managing unidirectional fault currents, enhance the safety and efficiency of power systems. On power lines equipped with directional relays, faults downstream (to the right) of the current transformer typically cause the fault current to lag the bus voltage by approximately 90 degrees, known as the forward direction. In contrast, upstream (left-side) faults may result in the fault current leading the bus voltage by nearly 90 degrees, termed the reverse...
85
Zones of Protection
123
In power systems, the entire setup is divided into protective zones to isolate faults and protect the rest of the network. These zones include generators, transformers, buses, transmission lines, distribution lines, and motors. Each zone can be visualized as a separate room in a house, with each room protected by its own circuit breaker.
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
Protective zones are defined by closed dashed lines, containing one or more components. A key characteristic of these zones is the strategic placement of...
123
Transmission Line Design Considerations
113
Aluminum has become the material of choice for overhead transmission lines, surpassing copper due to its abundance and cost-effectiveness. The most prevalent type is the aluminum conductor, steel-reinforced (ACSR), which combines aluminum strands around a steel core. Other variants include all-aluminum conductors (AAC), all-aluminum alloy conductors (AAAC), aluminum conductor alloy-reinforced (ACAR), and aluminum-clad steel conductors. Advanced designs, such as aluminum conductors with steel...