在高海拔的电磁脉冲下,10kV的典型配电变压器的响应特征
Xiaoyu Zhou1, Shiji Li1, Junna Li1
1State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University, Xi'an 710024, People's Republic of China.
The Review of scientific instruments
|July 21, 2025
概括
高空的电磁脉冲 (HEMP) 可以损坏分配变压器. 这项研究发现了一台10千伏变压器.
科学领域:
- 电气工程 电气工程
- 电磁学 电磁学 电磁学 电磁学
- 电力系统 电力系统
背景情况:
- 高空电磁脉冲 (HEMP) 对电力分配系统构成重大威胁.
- 连接HEMP与空中线路可以诱导损坏导电效应.
研究的目的:
- 为了研究HEMP诱导的传导效应在10千伏配电变压器上.
- 在HEMP下确定变压器绕线内的损坏值和电压分布.
主要方法:
- 使用传输线路理论进行HEMP合的理论分析.
- 使用模拟和物理平台的综合测试系统进行实验验证.
主要成果:
- 10千伏配电变压器的损坏门为267.5千伏.
- 观察到显著的不均的电压分布,最大值在第一个转时.
结论:
- 变压器线圈的第一个回转最容易由于集中的介电应力而导致绝缘断裂.
- 了解这些影响对于保护配电变压器免受HEMP威胁至关重要.
相关概念视频
Transformers in Distribution System
159
Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
159
Instrument Transformers
143
Instrument transformers, comprising voltage transformers (VTs) and current transformers (CTs), play crucial roles in power substations by providing isolated replicas of current or voltage for measurement and protection purposes. Voltage transformers reduce the primary voltage to levels suitable for relay operation and measurement, while current transformers scale down the primary current. The primary winding of a current transformer often consists of a single turn, achieved by threading the...
143
Secondary Distribution
138
Secondary distribution systems provide electrical energy at the utilization voltage levels from distribution transformers to customer meters. Typical secondary voltages in the United States include 120/240 V for residential use, 208Y/120 V for residential and commercial use, and 480Y/277 V for industrial and high-rise commercial use.
In residential areas, 120/240 V single-phase, three-wire service is commonly used for lighting, outlets, and large appliances. Urban areas with high-density loads...
In residential areas, 120/240 V single-phase, three-wire service is commonly used for lighting, outlets, and large appliances. Urban areas with high-density loads...
138
Insulation Coordination
232
Insulation coordination is the process of matching electric equipment's insulation strength with protective device characteristics to protect the equipment against expected overvoltages. This selection is based on engineering judgment and cost. Equipment can generally withstand short-duration high transient overvoltages, but repeated tests with identical waveforms can yield inconsistent results. As a result, standard impulse voltage waveforms are used for testing, defined by specific times...
232
Energy Losses in Transformers
980
In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality, the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
980
Primary Distribution
152
Primary distribution systems deliver electrical power from substations to consumers through various voltage classes, with 15-kV class voltages being predominant among U.S. utilities. Older 2.5- and 5-kV classes are being replaced by 15-kV primaries, while higher 25- to 34.5-kV classes are used in high-density urban areas and rural regions with long feeders. Three-phase, four-wire multigrounded systems are widely employed for balanced power delivery, using the neutral wire as a grounding point.
152