改进的人工生态系统优化器在中小型配电变压器参数识别方面的能力
Abdelmonem Draz1, Hossam Ashraf2, Ahmed R El Shamy3,4
1Electrical Power and Machines Department, Faculty of Engineering, Zagazig University, Zagazig, 44519, Egypt. aaderaz@zu.edu.eg.
Scientific reports
|September 12, 2025
概括
本研究介绍了一种改进的人工生态系统优化器 (IAEO),用于准确的分配变压器建模. IAEO在参数估计方面表现优于其他方法,实现更低的误差和更好的效率和电压调节预测.
科学领域:
- 电气工程 电气工程
- 计算智能是一种计算智能.
- 电力系统 电力系统
背景情况:
- 分配变压器 (TX) 的准确建模对于电力系统分析和运行至关重要.
- 现有的优化算法可能无法为TX参数估计提供足够的准确性.
研究的目的:
- 提出和验证一个改进的人工生态系统优化器 (IAEO),用于准确的分布TXs的参数估计.
- 将IAEO的性能与各种已建立的优化算法进行比较.
主要方法:
- 实施IAEO算法用于TX参数估计.
- 使用绝对错误总和 (SAE) 作为目标函数进行比较分析.
- 评估TX性能指标,包括效率和电压调节 (VR).
主要成果:
- IAEO在4kVA (1.12e-5) 和15kVA (0.0322) 的TX中取得了最低的SAE,表现优于竞争对手.
- IAEO准确地预测了TX稳定状态特征,例如在36.2%的负载下 (112.5kVA TX) 的峰值效率.
- 在额定领先功率因子条件下,对167kVA TX观察到高达-8%的负VR.
结论:
- 拟议的IAEO在分布TX参数估计方面表现出卓越的表现.
- IAEO提供了对TX运行特征的准确见解,包括效率和电压调节.
- 统计分析证实了IAEO强而高效的优化趋势.
相关概念视频
Transformers in Distribution System
498
Transformers in distribution systems can be broadly categorized into distribution substation transformers and other distribution transformers. They are crucial for stepping down high transmission voltages to levels suitable for distribution and end-user applications.
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
Distribution substation transformers come in various ratings and typically use mineral oil for insulation and cooling. To prevent moisture and air from entering the oil, some transformers use an inert gas like nitrogen to fill the...
498
Transformers with Off-Nominal Turns Ratios
523
In scenarios involving parallel transformers with disparate ratings, developing per-unit models requires accommodating off-nominal turns ratios. This situation arises when the selected base voltages are not proportional to the transformer’s voltage ratings. Consider a transformer where the rated voltages are related by the term a. If the chosen voltage bases satisfy a relationship involving term b, term c is defined as the ratio of these bases. This ratio is then substituted into the...
523
Instrument Transformers
439
Instrument transformers, comprising voltage transformers (VTs) and current transformers (CTs), play crucial roles in power substations by providing isolated replicas of current or voltage for measurement and protection purposes. Voltage transformers reduce the primary voltage to levels suitable for relay operation and measurement, while current transformers scale down the primary current. The primary winding of a current transformer often consists of a single turn, achieved by threading the...
439
Energy Losses in Transformers
1.3K
In an ideal transformer, it is assumed that there are no energy losses, and, hence, all the power at the primary winding is transferred to the secondary winding. However, in reality, the transformers always have some energy losses, and, hence, the output power obtained at the secondary winding is less than the input power at the primary winding due to energy losses.
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
1.3K
Equivalent Circuits for Practical Transformers
1.4K
The practical equivalent circuits of single-phase two-winding transformers exhibit significant deviations from their idealized versions due to the inherent properties of winding resistance and finite core permeability. These properties result in real and reactive power losses, affecting the transformer's performance. Understanding these deviations is crucial for designing more efficient transformers.
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
1.4K
Control of Power Flow
677
There are several methods to control power flow in power systems:
677