Experimental study of ventilation performance and contaminant distribution of underfloor ventilation systems vs.
1Department of Mechanical Engineering, Hong Kong University of Science and Technology, Clear Water Bay, Hong Kong, China. meyhchao@ust.hk
Unlabelled:
Ventilation performance and pollutant distribution in a traditional ceiling-type ventilation system, a top-return (TR)-type and a floor-return (FR)-type underfloor ventilation systems were performed in a controlled experimental room. Tracer gas method was utilized to determine the age of air and the contaminant removal effectiveness. Tobacco smoke was also introduced to study the particle-phase pollutant distribution. The TR system delivered conditioned air more efficiently in the occupied zone and exhibited higher gaseous contaminant removal effectiveness. It also showed the lowest smoke particle concentration compared with the other two systems. The FR system showed better ventilation performance over the mixing system at the space that was close to the floor supply outlet and at the lower height level. The FR system was less effective than the TR system in removing buoyant tobacco smoke particles at the upper part of the room indicating its highly localized characteristics. Differences in experimental conditions between the present and the previous studies and their effects on the experimental results are discussed. In general, the experimental data suggested that both types of the underfloor ventilation systems have the potential of improving air quality at the breathing zone over the ceiling-based mixing system with suitable designs.
Practical Implications:
This study shows the possibility of improving indoor air quality using underfloor ventilation systems compared with the traditional ceiling-based ventilation system. However, different configurations of the underfloor ventilation system show various ventilation characteristics. The engineers should consider these features when implementing an underfloor ventilation design. The top-return (TR) configuration improves indoor air quality by creating a displacement-like flow pattern while the floor-return (FR) configuration shows highly localized ventilation characteristics. The FR configuration improved the indoor air quality at spaces near the floor diffusers and up to certain heights.
Related Concept Videos
Assessment of Ventilation I: Respiratory Rate
A Ventilation assessment is critical for monitoring a patient's health status. Respiration, one of the most accessible vital signs, provides insights into the function of numerous body systems and can indicate serious health issues, such as brainstem injuries from head trauma.
Critical Guidelines for Assessing Ventilation:
Factors Affecting Pulmonary Ventilation
Alveolar Surface Tension
The alveolar fluid lines the luminal surface of the alveoli and exerts a force called surface tension. This force is caused by the polar water molecules in the liquid being more strongly attracted to each...