Inductive sensor performance in partial discharges and noise separation by means of spectral power ratios
Jorge Alfredo Ardila-Rey1, Mónica Victoria Rojas-Moreno2, Juan Manuel Martínez-Tarifa3
1Escuela Politécnica Superior, Departamento de Ingeniería Eléctrica, Universidad Carlos III de Madrid, Avenida de la Universidad 30, Leganés, Madrid 28911, Spain. jardila@ing.uc3m.es (
Abstract:
Partial discharge (PD) detection is a standardized technique to qualify electrical insulation in machines and power cables. Several techniques that analyze the waveform of the pulses have been proposed to discriminate noise from PD activity. Among them, spectral power ratio representation shows great flexibility in the separation of the sources of PD. Mapping spectral power ratios in two-dimensional plots leads to clusters of points which group pulses with similar characteristics. The position in the map depends on the nature of the partial discharge, the setup and the frequency response of the sensors. If these clusters are clearly separated, the subsequent task of identifying the source of the discharge is straightforward so the distance between clusters can be a figure of merit to suggest the best option for PD recognition. In this paper, two inductive sensors with different frequency responses to pulsed signals, a high frequency current transformer and an inductive loop sensor, are analyzed to test their performance in detecting and separating the sources of partial discharges.
More Related Videos
11:54Microfluidic Platform with Multiplexed Electronic Detection for Spatial Tracking of Particles
Published on: March 13, 2017
07:02Investigating the Potential of Singly Curved Thin Piezoelectric Transducers for Energy Harvesting and Structural Health Monitoring
Published on: November 14, 2025
Related Concept Videos
Tandem Mass Spectrometry
Inductively Coupled Plasma Atomic Emission Spectroscopy: Instrumentation
There are three main types of inductively coupled plasma atomic emission spectroscopy (ICP-AES) instruments: sequential, simultaneous multichannel, and Fourier transform instruments, with the latter being less commonly used....
¹³C NMR: ¹H–¹³C Decoupling
A broadband decoupling technique is used to simplify these complex, sometimes overlapping, signals. Broadband decoupling relies on a...
Discrete Fourier Transform
High-Performance Liquid Chromatography: Types of Detectors
Double Resonance Techniques: Overview
Spin decoupling is usually achieved by...