Related Experiment Video
Updated: Apr 25, 2026

Real-Time DC-dynamic Biasing Method for Switching Time Improvement in Severely Underdamped Fringing-field Electrostatic MEMS Actuators
Published on: August 15, 2014
Method to eliminate flux linkage DC component in load transformer for static transfer switch
Yu He1, Chengxiong Mao1, Jiming Lu1
1State Key Laboratory of Advanced Electromagnetic and Technology, Huazhong University of Science and Technology, Wuhan 430074, China.
Static transfer switches (STS) improve power quality but cause transformer inrush current. This study presents a method to eliminate DC components by transferring phases when flux linkages equalize, preventing damage.
Area of Science:
- Electrical Engineering
- Power Systems Engineering
Background:
- Sensitive industrial and commercial loads require reliable power quality, often using static transfer switches (STS).
- STS transfers can induce severe inrush currents (2-30 p.u.) in load transformers due to DC flux components.
- This inrush current risks disoperation of protective devices and transformer damage.
Purpose of the Study:
- To analyze flux linkage changes during STS transfer.
- To develop a method for calculating optimal transfer timing to eliminate inrush current.
- To validate the proposed transfer method through simulation and experiments.
Main Methods:
- Analysis of flux linkage variations in transformer windings during the transfer process.
- Calculation of the precise switching instant based on residual and prospective flux linkages.
- Implementation and testing of the developed transfer timing method using simulations and laboratory experiments.
Main Results:
- The study successfully analyzed the dynamic flux linkage behavior in transformers during STS operation.
- A novel method for determining the optimal phase transfer time was developed, effectively mitigating DC flux components.
- Simulations and experimental results confirmed the significant reduction in inrush current, validating the proposed technique.
Conclusions:
- The developed phase transfer method effectively eliminates the DC component, preventing severe inrush currents in transformers.
- This technique enhances the reliability and safety of power systems employing static transfer switches.
- The findings offer a practical solution for protecting transformers and ensuring stable power supply to sensitive loads.
Related Concept Videos
Reducing Line Loss
With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss...
Equivalent Circuits for Practical Transformers
In a practical transformer, each winding exhibits resistance and leakage reactance. The...
Three-Phase Short Circuit—Unloaded Synchronous Machine
This behavior occurs due to the magnetic flux produced by the short-circuit armature currents. Initially, these currents follow high-reluctance paths but eventually shift to...
Energy Losses in Transformers
There are four main reasons for energy losses in transformers.
The first cause can be the high resistance of the...
Fast Decoupled and DC Powerflow
Transformers
The iron core has a substantial relative permeability. Therefore, the magnetic field lines generated due to the current in one winding are almost entirely confined within the core, such that the same magnetic flux permeates each turn of both...