An improved low-voltage ride-through performance of DFIG based wind plant using stator dynamic composite fault
P K Gayen1, D Chatterjee2, S K Goswami2
1Electrical Engineering Department, Kalyani Government Engineering College, Kalyani, Nadia 741235, India.
ISA Transactions
|February 16, 2016
Summary
This study introduces a stator dynamic composite fault current limiter (SDCFCL) to improve the low-voltage ride-through (LVRT) of doubly fed induction generators (DFIGs). The SDCFCL effectively limits rotor overcurrent and overvoltage during grid faults.
Area of Science:
- Electrical Engineering
- Power Systems Engineering
- Renewable Energy Integration
Background:
- Grid-connected doubly fed induction generators (DFIGs) are crucial for renewable energy but susceptible to grid faults.
- Maintaining grid stability during faults requires robust protection mechanisms for DFIGs.
- Existing protection schemes like dynamic rotor current limiters (RCL) have limitations in fully mitigating fault impacts.
Purpose of the Study:
- To propose and evaluate an enhanced low-voltage ride-through (LVRT) strategy for grid-connected DFIGs.
- To introduce a novel stator dynamic composite fault current limiter (SDCFCL) for improved fault tolerance.
- To demonstrate the superiority of the SDCFCL over conventional methods in managing fault conditions.
Main Methods:
- Development of a stator dynamic composite fault current limiter (SDCFCL) circuit.
- The SDCFCL incorporates a series resistor-inductor combination and a parallel bidirectional semiconductor switch.
- Simulation studies using a grid-integrated 2.0MW DFIG model to validate the proposed SDCFCL performance.
Main Results:
- The SDCFCL effectively reduces rotor induced open circuit voltage by increasing stator inductance.
- The SDCFCL concurrently increases rotor impedance, limiting rotor circuit overcurrent and overvoltage.
- Simulation results show the SDCFCL provides more secure protection compared to conventional RCL during various fault scenarios.
Conclusions:
- The proposed SDCFCL significantly enhances the LVRT performance of grid-connected DFIGs.
- The SDCFCL offers a more effective and secure solution for mitigating rotor overcurrent and overvoltage during grid faults.
- The SDCFCL is a promising protection strategy for improving the reliability of DFIG-based power systems.
Related Concept Videos
Generator Voltage Control
775
Generator voltage control is crucial for maintaining the stable operation of synchronous generators and wind turbines. In older models, a DC generator driven by the rotor delivers DC power to the rotor's field winding, and the power is transferred through slip rings and brushes. In the latest models, static or brushless exciters are used. Static exciters rectify AC power from the generator terminals and then transfer the DC power directly to the rotor. Brushless exciters, on the other hand, use...
775
Wind Turbine Machine Models
677
In the growing field of wind energy, incorporating wind turbine models into transient stability analysis is essential. Induction and synchronous machines are the primary models used, with induction machines being prevalent due to their simplicity and reliability.
Induction machines interact through the rotating magnetic field generated by the stator and the rotor. The key parameter is slip, which is the difference between synchronous speed and rotor speed relative to synchronous speed. Slip is...
Induction machines interact through the rotating magnetic field generated by the stator and the rotor. The key parameter is slip, which is the difference between synchronous speed and rotor speed relative to synchronous speed. Slip is...
677
Turbine-Governor Control
1.1K
Turbine-governor control is crucial for maintaining power system stability by balancing turbine mechanical power output with electrical load demand. This mechanism ensures that generator frequency and rotor speed are within acceptable limits during load variations. Turbine-generator units store kinetic energy due to their rotating masses; this energy is released to meet the load requirement when the load increases. The electrical torque of turbines rises to meet the demand, whereas the...
1.1K
Series R—L Circuit Transients
482
In a series resistor-inductor (R-L) circuit, closing the switch at the start of the time period simulates a three-phase short circuit, a fault condition where all three phases of an unloaded synchronous machine are short-circuited. When there is no fault impedance and no initial current, the initial voltage is determined by the phase angle of the source voltage.
Using Kirchhoff's Voltage Law (KVL) to analyze this circuit helps determine the total asymmetrical fault current, which consists...
Using Kirchhoff's Voltage Law (KVL) to analyze this circuit helps determine the total asymmetrical fault current, which consists...
482
Generation of Three-Phase Voltage
957
A three-phase AC generator has a rotor with a rotating magnet placed within the stator mounted with the stationary three-phase winding to generate three-phase voltages via mutual induction. These windings are evenly distributed around the inner circumference of the stator and are arranged 120 electrical degrees apart. Three-phase stator windings consist of three separate coils or groups of coils, known as phases, each connected in Y (star) configuration or Delta configuration.
As the rotor...
As the rotor...
957
DC Generator
2.5K
An alternator converts mechanical energy into electrical energy that varies sinusoidally, resulting in AC current. Meanwhile, a DC generator converts mechanical energy into electrical energy, which are DC pulses with the same polarity. The construction of a DC generator is similar to that of an alternator, except that the pair of slip rings is replaced by a single split ring, also called a commutator. The commutator functions like a periodic rotary switch; it changes the contacts with the...
2.5K